| Plan Review Notes For Permit 16090925 |
| Permit Number |
16090925 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-09-28 18:58:22 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE EXISTING SINGLE FAMILY STRUCTURE HAS A | | | IMPROVEMENT VALUE OF MORE THAN $300,000.00. SECTION | | | 708.8 OF THE FBC EXISTING BUILDING REQUIRES: (A) ROOF | | | TO WALL CONNECTIONS SHALL BE IMPROVED AS REQUIRED BY | | | SECTION 708.8.1. | | | (B) MANDATED RETROFITS OF THE ROOF-TO-WALL CONNECTION | | | SHALL NOT BE REQUIRED BEYOND A 15-PERCENT INCREASE IN | | | THE COST OF REROOFING. | | | SHOW HOW THIS WILL BE ACCOMPLISHED. |
|