| Plan Review Notes For Permit 16090911 |
| Permit Number |
16090911 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-09-28 07:36:26 | | | | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SPECIFY THE APPROVED ROOFING ASSEMBLY, FASTENING | | | OPTION AND MAXIMUM DESIGN PRESSURE LISTED IN THE TAMKO | | | PRODUCT APPROVAL ( NOA NO. 12-1003.05 ) WILL BE | | | INSTALLED. FBC 107.2.1 | | | | | | 2) SUBMIT TWO SETS OF SIGNED AND SEALED RAS 117 | | | CALCULATIONS FOR ENHANCED FASTENING OF THE INSULATION | | | AND OR BASE SHEET AS REQUIRED BY LIMITATION NUMBER 7 ON | | | PAGE 14 OF NOA NO. 12-1003.05. FBC 107.2.1.3 | | | | | | 3) THE EXPOSURE CATEGORY FOR THIS PROJECT IS D PER FBC | | | R301.2.1.4.3. | | | |
|