| Plan Review Notes For Permit 16090903 |
| Permit Number |
16090903 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2016-11-08 11:32:49 | 1) SHT. A2.02 - THE ROOF PLAN IS ALMOST IMPOSSIBLE TO | | | READ DUE TO THE BACKGROUND DOTS. SUBMIT A CLEAN ROOF | | | PLAN FOR REVIEW. WPB AMEND. TO FBC SEC. 107.2.1. 2ND | | | REQUEST. | | | 2) SHT. A8.04 - DETAIL # 10 - THE LOCATION OF OVERFLOW | | | SCUPPERS IN THE PARAPET WALL SHALL COMPLY WITH 2014 FBC | | | SEC. 1503.4.2.1. | | | 3) SHT. A8.03 - VANITY TOP PLAN- THERE IS A NOTE THAT | | | READS "FIRST FLOOR ONLY." CLARIFY. | | | 4) SHT. A0.02 - THERE IS A CLOUDED NOTE AT THE TOP OF | | | THE PAGE THAT READS " PROVIDE WOOD BLOCKING IN ALL | | | FIRST FLOOR UNITS FOR FUTURE HANDICAP GRAB BARS". WOOD | | | BLOCKING SHALL BE PROVIDED IN ALL UNITS PER THE FHA. | | | 5) SHT. P5.01 - RISER S/JS - THE RISER SHOWS THE MOP | | | SINKS ON LEVELS #2 & #3 BUT RISER W/JS SHOWS THE WATER | | | SUPPLY TO THE MOP SINKS REMOVED. CLARIFY. | | | 6) SHT. P1.01 - THE HUB DRAIN RECEIVING THE DISCHARGE | | | FROM THE ELEVATOR SUMP SHALL BE EQUIPPED WITH A TRAP | | | PRIMER PER 2014 FPC SEC.1002.4. | | | 7) A2.01 - REMOVE THE BACKGROUND DOTS FROM THE FLOOR | | | PLAN. IT IS VERY DIFFICULT TO SE THE CLEAR FLOOR SPACE | | | FOR THE FIXTURES AND COMPLIANCE WITH THE FHA. | | | | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|