Plan Review Notes
Plan Review Notes For Permit 16090903
Permit Number 16090903
Review Stop P
Sequence Number 3
Notes
Date Text
2016-11-08 11:32:491) SHT. A2.02 - THE ROOF PLAN IS ALMOST IMPOSSIBLE TO
 READ DUE TO THE BACKGROUND DOTS. SUBMIT A CLEAN ROOF
 PLAN FOR REVIEW. WPB AMEND. TO FBC SEC. 107.2.1. 2ND
 REQUEST.
 2) SHT. A8.04 - DETAIL # 10 - THE LOCATION OF OVERFLOW
 SCUPPERS IN THE PARAPET WALL SHALL COMPLY WITH 2014 FBC
 SEC. 1503.4.2.1.
 3) SHT. A8.03 - VANITY TOP PLAN- THERE IS A NOTE THAT
 READS "FIRST FLOOR ONLY." CLARIFY.
 4) SHT. A0.02 - THERE IS A CLOUDED NOTE AT THE TOP OF
 THE PAGE THAT READS " PROVIDE WOOD BLOCKING IN ALL
 FIRST FLOOR UNITS FOR FUTURE HANDICAP GRAB BARS". WOOD
 BLOCKING SHALL BE PROVIDED IN ALL UNITS PER THE FHA.
 5) SHT. P5.01 - RISER S/JS - THE RISER SHOWS THE MOP
 SINKS ON LEVELS #2 & #3 BUT RISER W/JS SHOWS THE WATER
 SUPPLY TO THE MOP SINKS REMOVED. CLARIFY.
 6) SHT. P1.01 - THE HUB DRAIN RECEIVING THE DISCHARGE
 FROM THE ELEVATOR SUMP SHALL BE EQUIPPED WITH A TRAP
 PRIMER PER 2014 FPC SEC.1002.4.
 7) A2.01 - REMOVE THE BACKGROUND DOTS FROM THE FLOOR
 PLAN. IT IS VERY DIFFICULT TO SE THE CLEAR FLOOR SPACE
 FOR THE FIXTURES AND COMPLIANCE WITH THE FHA.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  