| 2016-11-17 13:34:33 | PERMIT #16090903 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | PASSED PROVISO: |
| | FAILURE TO COMPLY WITH THE PROVISO COMMENTS BELOW MAY |
| | RESULT IN A FAILED INSPECTION. |
| | |
| | 1) ENGINEERED FIRE ALARM AND FIRE SPRINKLER |
| | CONSTRUCTION DOCUMENTS ARE REQUIRED FOR A GENERAL |
| | BUILDING PERMIT. AFTER THE BUILDING PERMIT HAS BEEN |
| | ISSUED, THE SUBCONTRACTORS CAN THEN SUBMIT SHOP |
| | DRAWINGS (CONFORMING TO THE ENGINEERED CONSTRUCTION |
| | DOCUMENTS) FOR A SUB-PERMIT. ****THESE DOCUMENTS ARE TO |
| | BE SUBMITTED AS A REVISION TO THE PLAN AS SOON AS |
| | POSSIBLE, SO THAT THEY MAY BE REVIEWED AND APPROVED, |
| | PRIOR TO THE SUB-CONTRACTOR OBTAINING A PERMIT. FAILURE |
| | TO DO SO MAY RESULT IN THE SUBCONTRACTOR'S PERMIT |
| | APPLICATION BEING DENIED.***** |
| | |
| | 2) PER NFPA 88A, SECTION 5.3.2: ALL ENCLOSED PARKING |
| | STRUCTURES SHALL BE VENTILATED BY A MECHANICAL SYSTEM |
| | CAPABLE OF PROVIDING A MINIMUM OF 1FT3/MIN PER FT2 OF |
| | FLOOR AREA. MECHANICAL VENTILATING SYSTEMS SHALL BE |
| | INSTALLED IN ACCORDANCE WITH NFPA 90A. DUCTWORK SHALL |
| | BE CONSTRUCTED OF NONCOMBUSTIBLE MATERIAL. *****THE |
| | ENGINEER OF RECORD SHALL SUBMIT A REVISION TO THIS |
| | PLAN, IN RESPONSE TO THIS COMMENT. THE RESPONSE MAY BE |
| | IN NARRATIVE FORM, BUT SHALL CLEARLY STATE HOW |
| | COMPLIANCE WITH THE ABOVE REFERENCED CAPABILITIES IS TO |
| | BE ACHIEVED. FAILURE TO DO SO WILL RESULT IN A FAILED |
| | INSPECTION.****** |
| | |
| | |