Plan Review Notes
Plan Review Notes For Permit 16090903
Permit Number 16090903
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2016-11-17 13:34:33PERMIT #16090903
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PASSED PROVISO:
 FAILURE TO COMPLY WITH THE PROVISO COMMENTS BELOW MAY
 RESULT IN A FAILED INSPECTION.
  
 1) ENGINEERED FIRE ALARM AND FIRE SPRINKLER
 CONSTRUCTION DOCUMENTS ARE REQUIRED FOR A GENERAL
 BUILDING PERMIT. AFTER THE BUILDING PERMIT HAS BEEN
 ISSUED, THE SUBCONTRACTORS CAN THEN SUBMIT SHOP
 DRAWINGS (CONFORMING TO THE ENGINEERED CONSTRUCTION
 DOCUMENTS) FOR A SUB-PERMIT. ****THESE DOCUMENTS ARE TO
 BE SUBMITTED AS A REVISION TO THE PLAN AS SOON AS
 POSSIBLE, SO THAT THEY MAY BE REVIEWED AND APPROVED,
 PRIOR TO THE SUB-CONTRACTOR OBTAINING A PERMIT. FAILURE
 TO DO SO MAY RESULT IN THE SUBCONTRACTOR'S PERMIT
 APPLICATION BEING DENIED.*****
  
 2) PER NFPA 88A, SECTION 5.3.2: ALL ENCLOSED PARKING
 STRUCTURES SHALL BE VENTILATED BY A MECHANICAL SYSTEM
 CAPABLE OF PROVIDING A MINIMUM OF 1FT3/MIN PER FT2 OF
 FLOOR AREA. MECHANICAL VENTILATING SYSTEMS SHALL BE
 INSTALLED IN ACCORDANCE WITH NFPA 90A. DUCTWORK SHALL
 BE CONSTRUCTED OF NONCOMBUSTIBLE MATERIAL. *****THE
 ENGINEER OF RECORD SHALL SUBMIT A REVISION TO THIS
 PLAN, IN RESPONSE TO THIS COMMENT. THE RESPONSE MAY BE
 IN NARRATIVE FORM, BUT SHALL CLEARLY STATE HOW
 COMPLIANCE WITH THE ABOVE REFERENCED CAPABILITIES IS TO
 BE ACHIEVED. FAILURE TO DO SO WILL RESULT IN A FAILED
 INSPECTION.******
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  