Plan Review Notes
Plan Review Notes For Permit 16090903
Permit Number 16090903
Review Stop P
Sequence Number 1
Notes
Date Text
2016-10-25 05:54:411) THERE ARE ALREADY BUILDING DIVISION STAMPS ON THE
 ARCHITECTURAL PLANS WITH THE PERMIT NUMBER #15120896 ON
 THE PLANS. THESE PLANS ARE FOR AN ENTIRELY DIFFERENT
 PERMIT NUMBER. WHY IS AN EXISTING SET OF PLANS THAT HAS
 ALREADY BEEN REVIEWED AND APPROVED BEING SUBMITTED FOR
 REVIEW? CLARIFY.
 2) SHT. A4.02 - UNIT B.1 & B.1R - THE 30 X 48 INCH
 CLEAR FLOOR SPACE REQUIRED FOR THE SHOWER IN THE THE
 MASTER BATH SHALL BE FLUSH WITH THE CONTROL WALL IN
 ACCORDANCE WITH REQUIREMENT # 7 OF THE FHA GUIDELINES.
 3) SHT. A8.03 - VANITY TOP PLAN - SHOWS THE WATER
 CLOSET 1' - 6" FROM THE ADJACENT WALL AND IT IS NOTED
 THAT IT IS FOR THE FIRST FLOOR UNITS ONLY. PER THE FHA
 GUIDELINES, A WING OR PRIVACY WALL MAY OVERLAP THE
 CLEAR FLOOR SPACE FOR THE WATER CLOSET, HOWEVER IT MUST
 BE AT LEAST 33 INCHES FROM THE OPPOSITE WALL. CLARIFY
 WHY IT IS NOTED THAT IT APPLIES TO THE FIRST FLOOR
 ONLY. IT SHOULD APPLY TO ALL UNITS.
 4) SHT.A0.02 - THERE IS A CLOUDED NOTE ON THE PLANS
 THAT STATES "ALL UNITS ARE HANDICAP ACCESSIBLE
 COMPLYING WITH ...." AND STATES THAT WOOD BLOCKING WILL
 BE PROVIDED IN ALL FIRST FLOOR UNITS FOR FUTURE GRAB
 BARS. WOOD BLOCKING SHALL BE PROVIDED IN ALL COVERED
 DWELLING UNITS FOR THE FUTURE INSTALLATION OF GRAB BARS
 PER THE FHA GUIDELINES. REVISE THIS NOTE TO INCLUDDE
 ALL COVEREDD DWELLING UNITS.
 5) SHT. P6.01 - NOTE #13 STATES THAT CPVC WILL BE USED
 FOR CONDENSATE DRAIN PIPING RUNOUTS TO THE UNITS. IF
 THE A/C CLOSET IS A RETURN AIR PLENUM, THE MATERIALS
 WITHIN THE PLENUM SHALL BE NONCOMBUSTIBLE OR SHALL BE
 LISTED AS HAVING A FLAME SPREAD INDEX OF NOT MORE THAN
 25 AND A SMOKE - DEVEELOPED INDEX OFF NOT MORE THAN 50
 WHEN TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723 PER
 THE 2014 FMC SEC.602.2.1. SUBMIT MANUFACTURER'S
 SPECIFICATIONS OF THE CPVC FOR REVIEW.
 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE OIL
 SMART PUMP SYSTEM. WPB AMEND. TO FBC SEC. 107.2.1.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  