2016-10-26 13:54:17BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16090903
 ADD: 7110 OKEECHOBEE BLVD. BLDG. # 6/ BLDG. TYPE: I
 CONT: ELEV8 CONSTRUCTION CO. / STEVE NAPIER
 TEL: 561-891-0414
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
 1ST REVIEW
 DATE: WED. OCT.26 /2016
 ACTION: DENIED
  
 1) THIS IS A THRESHOLD BUILDING AND THE THRESHOLD
 AGREEMENT WILL NEED AN ADDENDUM FOR THE ADDITIONAL
 BUILDINGS THAT ARE TO BE INSPECTED BY THE THRESHOLD
 INSPECTOR.
  
 BUILDING PROVISO
  
 NOTE: THIS REVIEW IS FOR BUILDING# 6. BUILDING TYPE I,
 NOT FOR THE SITE PLAN, OR ANY ASSOCIATED AMENITIES.
 SURVEY AND SITE SOILS REPORT ARE FILED UNDER PERMIT
 16020377 THE RECREATION/ LEASING BUILDING.
 PLEASE NOTE : THE BUILDING OFFICIAL HAS AGREED TO THE
 BUILDING EVALUATION COST SUBMITTED TO HIM. THE 4
 SUB-PERMITS THAT ARE A NO COST IF THEY CAME IN AT THE
 TIME OF THE PRIME PERMIT ARE MECHANICAL, ELECTRICAL,
 PLUMBING & ROOFING. IF THEY COME IN AFTER THE PRIME
 PERMIT WAS CREATED THEY ARE A $80.00 SUB-PERMIT, THE
 $80.00 IS AN ADMINISTRATIVE FEE.
 THE VALUE OF THE SUB-PERMITS WHERE THE VALUE OF THE
 PERMIT IS NOT COVERED UNDER THE PRIME PERMIT NEED TO BE
 DEDUCTED FROM THE $4,000,000.00 STATED FROM BUILDING #
 3. THE PERMIT VALUE FOR BUILDING # 6 THE VALUE OF
 $3,903,245.00 IS LISTED. IT APPEARS THE VALUE OF THE
 PERMITS NOT COVERED UNDER THE MASTER HAVE THEIR VALUE
 ALREADY DELETED. PLEASE PROVIDE THE VALUE OF TOUGHS
 PERMITS. THESE PERMITS INCLUDE, FIRE SPRINKLERS, FIRE
 ALARMS, ALL LOW VOLTAGE PERMITS.
 PLEASE NOTE ALL OTHER PERMITS NOT ASSOCIATED WITH THE
 BUILDING ARE CONSIDERED PROJECT COST AND WILL BE
 PERMITTED SEPARATELY. SITE CLEARING, DEMOLITION OF
 STRUCTURES, UNDERGROUND UTILITIES, PAVING, SEAL COATING
 & STRIPING, SIDEWALKS, IRRIGATION, LANDSCAPE, POOLS,
 POOL DECK IF NOT INCLUDED IN THE POOL CONTRACT,
 FENCING, OUT BUILDINGS, SIGNAGE ETC.
 1) BUILDING PROVISO: SHORING & RESHORING PLANS TO BE
 SUBMITTED AS A DEFERRED SUBMITTAL, TO BE REVIEWED BY
 THE ENGINEER OF RECORD, APPROVED BEFORE SUBMITTAL TO
 THE BUILDING DEPARTMENT.
 2A-2E) BUILDING PROVISO: PRODUCT APPROVALS TO BE
 DEFERRED SUBMITTALS.
 2B) DEFERRED SUBMITTALS: COMPONENTS & CLADDING. 2014
 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS 7 ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 2C) DEFERRED. 107.3.4.1 THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 2D) DEFERRED. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING .
  
 2E) DEFERRED. FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED. IF SO
 RAS 117 CALCULATIONS ARE REQUIRED BY EITHER A FLORIDA
 ARCHITECT OR ENGINEER.
 2F) COMPLIED. A/C STANDS.
  
 3) BUILDING PROVISO/ DEFERRED SUBMITTAL:
 3A) DEFERRED SUBMITTAL. NOTE THIS NOTE APPLIES TO
 FLOORS 2-4 ONLY. FBC-B 2014 1207.3 STRUCTURE-BORNE
 SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS
 OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 3B) DEFERRED SUBMITTAL . THIS NOTE APPLIES TO WALLS AS
 WELL AS FLOORS!!! ON ALL FLOORS. WALL TYPES FOUND ON
 SHEET A8.01, THE WALL TYPES DO NOT PROVIDE THE REQUIRED
 STC RATING NOR TEST RESULTS IN ACCORDANCE WITH: FBC-B
 2014 1207.2 AIR-BORNE SOUND. WALLS, PARTITIONS AND
 FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS FROM
 EACH OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL HAVE A
 SOUND TRANSMISSION CLASS (STC) OF NOT LESS THAN 50 (45
 IF FIELD TESTED) FOR AIR-BORNE NOISE WHEN TESTED IN
 ACCORDANCE WITH ASTM E 90.
  
 3C) DEFERRED SUBMITTAL. THIS IS A VERY RESTRICTIVE
 REQUIREMENT!!!!!! TYPE III-TYPE V CONSTRUCTION:
 FBC-B-2014 720.2 CONCEALED INSTALLATION. INSULATING
 MATERIALS, WHERE CONCEALED AS INSTALLED IN BUILDINGS OF
 ANY TYPE OF CONSTRUCTION, SHALL HAVE A FLAME SPREAD
 INDEX OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX
 OF NOT MORE THAN 450.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 4E) PROVISO: THE GARAGES ALL SHOW ON SHEET E1.01 &
 E5.01 CIRCUITRY TO INCLUDE A GARAGE DOOR OPENER. PLEASE
 PROVIDE COMPLIANCE WITH THE 2014 FBC-B 406.3.5
 AUTOMATIC GARAGE DOOR OPENERS. AUTOMATIC GARAGE DOOR
 OPENERS, IF PROVIDED, SHALL BE LISTED IN ACCORDANCE
 WITH UL 325. IF THERE IS A POWER FAILURE OR A
 MECHANICAL BREAKDOWN WITHOUT ANY OTHER MEANS OF EGRESS
 HOW WILL ENTRY INTO A GARAGE BE ACHIEVED. 107.2.1.3.
 ADDITIONAL INFORMATION IS REQUIRED.
  
 5) PROVISO: THE HEIGHT OF THE SLIDING GLASS DOOR SILL
 WILL BE DETERMINED BY THE SLIDING GLASS DOOR PRODUCT
 APPROVAL AND ASSOCIATED PRESSURES. SHEET A8.02 .
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  