2016-10-26 15:34:452ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16090886
 10/3/2016
  
 1) PROVIDE A CHILLED WATER PIPING PLAN SHOWING ALL NEW
 PIPING RUNS AND POINTS OF CONNECTIONS TO EXISTING
 PIPING. PLEASE INCLUDE DETAILS- TYPE AND SIZE OF PIPES,
 AND PIPE INSULATION.
  
 2) ENERGY FORM C402-2014: A) THE FORM MUST BE SIGNED BY
 THE PERSON WHO PREPARED IT, AND BY THE OWNER/AGENT. B)
 SHOW COMPLIANCE DATA FOR THE CHILLED WATER PIPING, FAN
 COIL UNITS, AND THE NEW REPLACEMENT WINDOWS- SECTION
 C101.4.3 FBC-14 ENERGY CONSERVATION.
  