Plan Review Notes
Plan Review Notes For Permit 16090886
Permit Number 16090886
Review Stop E
Sequence Number 2
Notes
Date Text
2016-10-26 10:19:542ND ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 PREVIOUS COMMENTS NOT ADDRESSED AND NEW DUE TO NEW
 SERVICES:
  
 1. NEW RISER SHEET SUBMITTED IS COMPLETELY NEW AND
 REQUIRES ADDITIONAL COMPLIANCE. PLEASE LABEL PER NEC
 230.2E THE TWO NEW SERVICES NOW SHOWN TO BUILDING WITH
 PERMANENT PLAQUE INDICATING PER VERBIAGE IN THE CODE. A
 NOTE WILL SUFFICE.
 2. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO
 INDICATE NEC 110.16. ARC FLASH WARNING SIGNS AND NEC
 110.24- AVAILABLE FAULT CURRENT- FIELD MARKINGS; SEE
 VERBIAGE IN CODE.
 3. PER NEC 702.4B1- MANUAL TRANSFER SWITCH AND NEC
 702.7 SIGNS-SIGNAGE REQUIREMENTS TO BE MET. SEE CODE;
 ADD NOTE TO RISER.
 1. PLEASE ADD A GENERAL NOTE TO INDICATED REQUIRED
 SEPARATE PERMITS FOR LOW VOLTAGE SYSTEMS AND SITE
 LIGHTING. FBC 107.3.5
 2. PER FBC EC 405.7- A MINIMUM OF 50% OF ALL 125V, 15
 AND 20AMP RECEPTACLES SHALL BE AUTOMATICALLY CONTROLLED
 WHERE INSTALLED IN PRIVATE OR OPEN OFFICES AND COMPUTER
 CLASSROOMS. THIS INCLUDES MODULAR PARTITIONS TOO. SHOW
 COMPLIANCE ACCORDINGLY.
 3. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING
 THIS PROJECT.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  