| Plan Review Notes For Permit 16090886 |
| Permit Number |
16090886 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-10-26 10:19:54 | 2ND ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 | | | PREVIOUS COMMENTS NOT ADDRESSED AND NEW DUE TO NEW | | | SERVICES: | | | | | | 1. NEW RISER SHEET SUBMITTED IS COMPLETELY NEW AND | | | REQUIRES ADDITIONAL COMPLIANCE. PLEASE LABEL PER NEC | | | 230.2E THE TWO NEW SERVICES NOW SHOWN TO BUILDING WITH | | | PERMANENT PLAQUE INDICATING PER VERBIAGE IN THE CODE. A | | | NOTE WILL SUFFICE. | | | 2. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO | | | INDICATE NEC 110.16. ARC FLASH WARNING SIGNS AND NEC | | | 110.24- AVAILABLE FAULT CURRENT- FIELD MARKINGS; SEE | | | VERBIAGE IN CODE. | | | 3. PER NEC 702.4B1- MANUAL TRANSFER SWITCH AND NEC | | | 702.7 SIGNS-SIGNAGE REQUIREMENTS TO BE MET. SEE CODE; | | | ADD NOTE TO RISER. | | | 1. PLEASE ADD A GENERAL NOTE TO INDICATED REQUIRED | | | SEPARATE PERMITS FOR LOW VOLTAGE SYSTEMS AND SITE | | | LIGHTING. FBC 107.3.5 | | | 2. PER FBC EC 405.7- A MINIMUM OF 50% OF ALL 125V, 15 | | | AND 20AMP RECEPTACLES SHALL BE AUTOMATICALLY CONTROLLED | | | WHERE INSTALLED IN PRIVATE OR OPEN OFFICES AND COMPUTER | | | CLASSROOMS. THIS INCLUDES MODULAR PARTITIONS TOO. SHOW | | | COMPLIANCE ACCORDINGLY. | | | 3. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE | | | TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING | | | THIS PROJECT. | | | | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | |
|