| 2016-10-22 09:17:30 | NATIONAL FLOOD INSURANCE PROGRAM (NFIP) |
| | W. P. B. PERMIT: 16090860 |
| | ADD: 1301 SUMMIT BLVD/ LORIKEET BIRD EXHIBIT |
| | CONT: GAST |
| | TEL: 561-281-1001 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 1ST REVIEW |
| | DATE: SAT. OCT 22/2016 |
| | ACTION: DENIED |
| | |
| | 1) THIS PROPERTY IS ALSO LOCATED IN A FLOOD ZONE. FBC |
| | BUILDING 1612 AND CITY OF WPB CODE OF ORDINANCES |
| | SECTION 94-546. STRUCTURE IS LOCATED IN AN "A 7" FLOOD |
| | ZONE, BFE ELEVATION 12 FEET NGVD. A FLOOD ELEVATION |
| | CERTIFICATE WILL BE REQUIRED. THE CITY OF WEST PALM |
| | BEACH IS STILL USING THE 1929 NGVD ELEVATION DATUM. NO |
| | FIS FOR THIS LOCATION. |
| | IMPORTANT CHANGE!!!! |
| | PLEASE REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS |
| | REQUIRE AN ADDITIONAL (1FOOT) FREEBOARD OF ELEVATION. |
| | CITY ORDINANCE CHANGE SEPT. 12/2016. PLEASE ALSO NOTE |
| | FOR FUTURE WORK IN THE CITY?S FLOOD ZONE AREAS, THE |
| | CITY COMMISSION & MAYOR WILL BE CHANGING THE FREEBOARD |
| | REQUIREMENTS TO (2 FOOT) FREEBOARD IN THE UPCOMING |
| | MONTHS. ALSO ON ALL FLOOD ZONE CERTIFICATES THE |
| | LATITUDE AND LONGITUDE ARE TO BE FILLED OUT WITH THE |
| | FRONT CENTER OF THE STRUCTURE BEING THE POINT GIVEN. |
| | DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE |
| | REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES |
| | REQUIRED: |
| | (2.1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF |
| | THE PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH |
| | FLOOR HEIGHT. 107.2.5.1 DESIGN FLOOD ELEVATIONS. |
| | 107.3.5.1.1(1) MINIMUM PLAN REVIEW COMMERCIAL |
| | BUILDINGS. FLOOD HAZARD AREAS, FLOOD ZONES, AND DESIGN |
| | FLOOD ELEVATIONS. |
| | |
| | (2.2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND |
| | ELEVATION CERTIFICATE IS REQUIRED. REQUIRED |
| | INSPECTIONS. 110.3.( 1.2.) IN FLOOD HAZARD AREAS, UPON |
| | PLACEMENT OF THE LOWEST FLOOR, INCLUDING BASEMENT, |
| | AND PRIOR TO FURTHER VERTICAL CONSTRUCTION, THE |
| | ELEVATION CERTIFICATION, REQUIRED IN SECTION 1612.5, |
| | SHALL BE SUBMITTED TO THE BUILDING OFFICIAL. |
| | |
| | (2.3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY |
| | OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE |
| | CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR |
| | ATTENDANTS. REQUIRED INSPECTIONS. 110.3.( 6.) FINAL |
| | INSPECTION. TO BE MADE AFTER THE BUILDING IS COMPLETED |
| | AND READY FOR OCCUPANCY.6.1. LOWEST FLOOR ELEVATION. IN |
| | FLOOD HAZARD AREAS, AS PART OF THE FINAL INSPECTION, A |
| | FINAL CERTIFICATION OF THE LOWEST FLOOR ELEVATION SHALL |
| | BE SUBMITTED TO THE AUTHORITY HAVING JURISDICTION. |
| | A/C PADS OR OTHER SLABS FOR GENERATORS |
| | FEMA NEW FORM AVAILABLE JUNE 13/2016. |
| | OMB NO. 1660-0008 |
| | EXPIRATION DATE: NOV. 30/2018 |
| | HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM |
| | |