| 2016-09-29 20:01:02 | ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| | |
| | JOB ADDRESS: 1301 SUMMIT BLVD. |
| | DESCRIPTION: CONSTRUCTION OF LORIKEET BIRD EXHIBIT TO |
| | INCLUDE SITE WORK CMU STRUCTURES, MECHANICAL, |
| | ELECTRICAL, ROOFING, ANIMAL CAGING |
| | MASTER PERMIT: 16090860 |
| | |
| | BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS. |
| | ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF |
| | SUBMITTED CORRECTIONS. |
| | |
| | 1. NEC 110.16 ARC-FLASH HAZARD WARNING: ELECTRICAL |
| | EQUIPMENT IN OTHER THAN DWELLING UNITS LIKELY TO |
| | REQUIRE SERVICE WHILE ENERGIZED SHALL BE FIELD MARKED |
| | TO WARN AGAINST POTENTIAL ARC-FAULT HAZARDS. |
| | 2. NEC 110.24: THE MAXIMUM AVAILABLE FAULT CURRENT |
| | SHALL BE DURABLY MARKED AND DATED ON ALL NON-DWELLING |
| | ELECTRICAL APPARATUS. |
| | 3. NEC 110.26(D) ILLUMINATION. ILLUMINATION SHALL BE |
| | PROVIDED FOR ALL WORKING SPACES ABOUT SERVICE |
| | EQUIPMENT, SWITCHBOARDS, AND PANELBOARDS. THIS LIGHT |
| | SHALL NOT BE CONTROLLED BY AUTOMATIC MEANS ONLY. |
| | 4. NEC 215.5 DIAGRAMS OF FEEDERS. A RISER DIAGRAM |
| | SHOWING FEEDER DETAILS ALONG WITH RESPECTIVE LOAD CALCS |
| | SHALL BE PROVIDED. THIS DIAGRAM SHALL INCLUDE CONDUCTOR |
| | SIZING AND INSULATION TYPE. FURTHERMORE, IT SHALL BE |
| | SITE SPECIFIC. THE SUBMITTED RISER DIAGRAM IS |
| | INCOMPLETE. |
| | 5. PROVIDE LOAD CALCS AND CIRCUIT DIRECTORY FOR PANEL X |
| | AND INCLUDE THAT IN THE ABOVE MENTIONED SERVICE LOAD |
| | CALCS. |
| | 6. FBC-E C405.7.3 VOLTAGE DROP. FEEDERS & CUSTOMER |
| | OWNED SERVICE CONDUCTORS SHALL BE SIZED FOR A MAXIMUM |
| | OF 2% VOLTAGE DROP. BRANCH CIRCUITS SHALL BE SIZED FOR |
| | A MAXIMUM OF 3% VOLTAGE DROP. SUBMIT VOLTAGE DROP |
| | CALCULATIONS FOR ALL FEEDERS. SHOW THE VARIOUS |
| | DISTANCES ON THE PLAN. |
| | 7. FBC-EC405.2.4 EXTERIOR LIGHTING. LIGHTING NOT |
| | DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE |
| | CONTROLLED BY EITHER A COMBINATION OF A PHOTO SENSOR |
| | AND A TIME SWITCH, OR AN ASTRONOMICAL TIME SWITCH. |
| | LIGHTING DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE |
| | CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR PHOTO |
| | SENSOR. ALL TIME SWITCHES SHALL BE CAPABLE OF RETAINING |
| | PROGRAMMING AND THE TIME SETTING DURING LOSS OF POWER |
| | FOR A PERIOD OF AT LEAST 10 HOURS. |
| | 8. FBC-EC405.2.2.2 OCCUPANCY SENSORS. OCCUPANCY SENSORS |
| | SHALL BE INSTALLED IN ALL CLASSROOMS, |
| | CONFERENCE/MEETING ROOMS, EMPLOYEE LUNCH AND BREAK |
| | ROOMS, PRIVATE OFFICES, RESTROOMS, STORAGE ROOMS AND |
| | JANITORIAL CLOSETS, AND OTHER SPACES 300 SQUARE FEET |
| | (28 M2) OR LESS ENCLOSED BY FLOOR-TO-CEILING HEIGHT |
| | PARTITIONS. THESE AUTOMATIC CONTROL DEVICES SHALL BE |
| | INSTALLED TO AUTOMATICALLY TURN OFF LIGHTS WITHIN 30 |
| | MINUTES OF ALL OCCUPANTS LEAVING THE SPACE, AND SHALL |
| | EITHER BE MANUAL ON OR SHALL BE CONTROLLED TO |
| | AUTOMATICALLY TURN THE LIGHTING ON TO NOT MORE THAN 50 |
| | PERCENT POWER. |
| | 9. CORRECT PANEL DP CIRCUIT DIRECTORY TO INCLUDE PANEL |
| | LH. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |