| Plan Review Notes For Permit 16090850 |
| Permit Number |
16090850 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-11-02 08:08:46 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #16090850 | | | 11/2/16 | | | | | | 1) SHEET R-1.2: PROVIDE DETAILS FOR ATTACHING THE | | | FLEXPACK CURB TO THE ROOF STRUCTURE. | | | | | | 2) R-1.2: THE FILE STATUS FOR NOA # 09-0804.05 IS | | | LISTED AS "CLOSED" ON THE MIAMI-DADE PRODUCT CONTROL | | | WEBSITE. PLEASE SELECT A ROOF STAND WITH A VALID NOA #. | | | | | | 3) SHEET S-2.0 MUST BE REVISED TO SHOW THE CORRECT | | | LOCATION OF THE FLEXPAK PER REFRIGERATION DRAWING | | | R-1.0. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|