2016-09-27 10:47:001ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16090850
 9/27/16
  
 1) THE MECHANICAL PLAN SHEETS APPEAR TO HAVE COPIED
 ENGINEER'S SIGNATURES, HOWEVER ORIGNINAL SIGNATURES ARE
 REQUIRED PER FLORIDA STATUTES AND SECTION 61G15-23.002
 FLORIDA ADMINISTRATIVE CODE.
  
 2) M2.1: TYPE C HARD DRAWN COPPER SPECIFIED FOR THE
 LIQUID LINE PIPING IS NOT IN COMPLIANCE WITH SECTIONS
 1107.5.2, 1107.5.3 WHICH ALLOWS THE USE OF TYPE ACR, OR
 TYPE K, L, OR M- PLEASE CORRECT.
  
 3) PROVIDE A MECHANICAL FLOOR PLAN LAYOUT SHOWING
 LOCATIONS OF ALL REFRIGERATION EQUIPMENT AND
 REFRIGERANT PIPING RUNS.
  
 4) EF-1: INCLUDE THE WALK-IN COOLER EVAPORATORS AND
 FLEXPAK IN THE EQUIPMENT SCHEDULE.
  
 5) PROVIDE WIND LOAD ENGINEERING FOR TIE DOWN AND
 ANCHORING OF ALL ROOFTOP REFRIGERATION EQUIPMENT-
 SECTION 301.15.
  
 6) THE $22,500.00 JOB COST ON THE APPLICATION APPEARS
 TO BE LOW FOR THE SCOPE OF THE PROPOSED WALK-IN COOLER
 AND REFRIGERATION PROJECT. PLEASE PROVIDE AN ITEMIZED
 LIST OF ALL LABOR, MATERIALS, AND EQUIPMENT TO BE
 INCLUDED UNDER THIS PERMIT APPLICATION AND WHICH COSTS
 WERE INCLUDED UNDER THE MAIN BUILDING PERMIT. REFER TO
 SECTION 109.3 WPB AMENDMENTS TO THE FBC-14 FBC, AND
  
 NOTE THAT VALUATION REFERENCES WILL INCLUDE THE LATEST
 PUBLISHED DATA OF MARSHALL-SWIFT VALUATION SERVICE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  