2016-12-15 12:03:061) SUBMIT FACTORY SIZING CALCULATIONS CREATED BY SCHIER
 FOR THE GREASE INTERCEPTOR IN ACCORDANCE WITH 2014 FPC
 SEC. 1003.2. THE SIZE, TYPE AND LOCATION OF EACH
 INTERCEPTOR SHALL BE APPROVED BY THE PLUMBING
 OFFFICIAL. CONTACT LEE SCHNEEWEISS OF SCHIER AT
 1-800-538-4792 FOR ASSISTANCE.
 2) PLEASE PROVIDE A SEQUENCE OF OPEREATIONS FOR THE
 SANITARY HOLDING TANKS. A RESPONSE WAS SUPPLIED IN THE
 NARRATIVE BUT THE INFORMATION NEEDS TO BE ON THE PLANS.
 WPB AMEND. TO FBC SEC. 107.2.1.
 3) SHT. A-761, DETAIL 04 - RESTROOMS #183 & #184 SHALL
 CONTAIN A HANDICAPPED ACCESSIBLE TOILET COMPARTMENT
 WITHIN EACH RESTROOM. 2014 FBC-ACCESS. SEC.213.3.1. THE
 REQUEST FOR RELIEF HAS BEEN FORWARDED TO ROBERT BROWN,
 BUILDING OFFICIAL.
 4) SHT. LS-201 - THE FITNESS ROOM SHALL BE CALCULATED
 AT 50 SQUARE FEET PER PERSON PER TABLE1004.1.2.THE
 RESPONSE NARRATIVE REFERS TO SHT. LS-201 BUT I COULD
 NOT FIND THIS REVISED INFORMATION ON THE SHEET.
 CLARIFY.
 5) SHT. P302 - INCLUDE THE EMERGENCY (OVERFLOW) STORM
 DRAINS ON THE STORM DRAIN RISER. SHOW THE PITCH OF THE
 HORIZONTAL DRAIN.
 6) SHT. A401 - SHOW THE LOCATION OF THE ROOF DRAINS AND
 OVERFLOW DRAINS ON THE PLAN.
 7) SHT. P202 - FLOOR DRAINS ARE SHOWN IN ROOMS #109,
 #190, #1191, #193, #233 & #290. THESE DRAINS ARE
 CONNECTED TO THE SANITARY AND WILL REQUIRE TRAP PRIMERS
 PER 2014 FPC SEC.1002.4.
 8) SHT. P302 - THERE ARE STILL SECTIONS OF THE SANITARY
 SYSTEM (VENTS, BUILDING DRAIN,..) THAT ARE NOT SIZED.
 WPB AMEND. TO FBC SEC. 107.2.1.
 9) SHT. A-761 - CLEARLY SHOW THE CONTROL WALL IN THE
 HANDICAPPED ACCESSIBLE TRANSFER SHOWERS. THE GRAPHICS
 ARE SO LIGHT THAT THE CONTROL WALL IS DIFFICULT TO
 DETERMINE. WPB AMEND. TO FBC SEC. 107.2.1.
 10) SUBMIT DETAILS FOR THE GENERATORS IN THE EQUIPMENT
 CORRAL. SUBMIT INFORMATION ON THE FUEL SOURCE FOR THE
 GENERATORS, PIPING DETAILS (IF APPLICABLE) ETC.WPB
 AMEND. TO FBC SEC. 107.2.1.2ND REQUEST.THE NARRATIVE
 REFERS TO THE ELECTRICAL PLANS FOR INFORMATION. I COULD
 NOT FIND ANY INFORMATION ON THE GENERATOR IN THE
 ELECTRICAL PLANS. CLARIFY.
 11) SHT. A-701 - DETAIL 01- G6 ACCESSIBLE SHOWER - THE
 SHOWER CONTROLS, FAUCET AND SHOWER SPRAY UNIT IN THE
 ACCESSIBLE TRANSFER SHOWERS SHALL BE LOCATED ON THE
 SIDE WALL OPPOSITE THE SEAT 38 INCHES MINIMUM AND 48
 INCHES MAXIMUM ABOVE THE SHOWER FLOOR AND SHALL BE
 LOCATED ON THE CONTRL WALL 15 INCHES MAXIMUM FROM THE
 CENTERLINE OF THE SEAT TOWARD THE SHOWER OPENING.2014
 FAC SEC.608.5.1. THE DETAIL SHOWS THIS AS AN "OPTIONAL
 SHOWER HEAD AND CONTROL LOCATION." THIS IS NOT
 OPTIONAL. CLEARLY SHOW COMPLIANCE WITH THIS CODE
 SECTION.
 12) GRAB BARS IN THE ACCESSIBLE TRANSFER SHOWERS SHALL
 COMPLY WITH 2014 FAC SEC.608.3.1. CLEARLY SHOW
 COMPLIANCE WITH THIS CODE SECTION ON THE PLANS.
 13) NOTE: THE FINISHED CLEAR INSIDE DIMENSIONS OF THE
 ACCESSIBLE TRANSFER SHOWERS SHALL BE 36 INCHES BY 36
 INCHES MEASURED AT THE CENTER POINTS OF OPPOSING SIDES.
 FINISHED DIMENSIONS OTHER THAN THIS IS NON-COMPLIANT.
 14) SHT. P-201 - WHERE IS THE SANITARY LINE FOR ROOM
 #187? 2ND REQUEST.
 15) CLEARLY SHOW THE LOCATION OF GRAB BARS IN THE
 HANDICAPPED ACCESSIBLE TRANSFER SHOWERS. COMPLY WITH
 2015 FBC SEC.608.3.1 AND FIGURE 608.3.1.
 15) THE FOLLOWING ITEMS WILL BE CONSIDERED DEFERRED
 SUBMITTALS. DOCUMENTATION SHALL BE SUBMITTED FOR REVIEW
 PRIOR TO WORK STARTING ON THESE ITEMS.
  
 1) MANUFACTURER'S SPECIFICATIONS FOR THE WATER TANK.
 2) MANUFACTURER'S SPECIFICATIONS FOR THE BLADDER TANK
 AND SIZE OF THE BLADDER TANK.
 3) DETAILS AND DIMENSIONS FOR THE ANCHORING OF THE
 WATER TANK, SIZE AND TYPE OF STRAPS, TRAFFIC PROTECTION
 FOR THE PUMPS, SPECS ON THE PUMPS, ETC.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW