| 2016-12-15 12:03:06 | 1) SUBMIT FACTORY SIZING CALCULATIONS CREATED BY SCHIER |
| | FOR THE GREASE INTERCEPTOR IN ACCORDANCE WITH 2014 FPC |
| | SEC. 1003.2. THE SIZE, TYPE AND LOCATION OF EACH |
| | INTERCEPTOR SHALL BE APPROVED BY THE PLUMBING |
| | OFFFICIAL. CONTACT LEE SCHNEEWEISS OF SCHIER AT |
| | 1-800-538-4792 FOR ASSISTANCE. |
| | 2) PLEASE PROVIDE A SEQUENCE OF OPEREATIONS FOR THE |
| | SANITARY HOLDING TANKS. A RESPONSE WAS SUPPLIED IN THE |
| | NARRATIVE BUT THE INFORMATION NEEDS TO BE ON THE PLANS. |
| | WPB AMEND. TO FBC SEC. 107.2.1. |
| | 3) SHT. A-761, DETAIL 04 - RESTROOMS #183 & #184 SHALL |
| | CONTAIN A HANDICAPPED ACCESSIBLE TOILET COMPARTMENT |
| | WITHIN EACH RESTROOM. 2014 FBC-ACCESS. SEC.213.3.1. THE |
| | REQUEST FOR RELIEF HAS BEEN FORWARDED TO ROBERT BROWN, |
| | BUILDING OFFICIAL. |
| | 4) SHT. LS-201 - THE FITNESS ROOM SHALL BE CALCULATED |
| | AT 50 SQUARE FEET PER PERSON PER TABLE1004.1.2.THE |
| | RESPONSE NARRATIVE REFERS TO SHT. LS-201 BUT I COULD |
| | NOT FIND THIS REVISED INFORMATION ON THE SHEET. |
| | CLARIFY. |
| | 5) SHT. P302 - INCLUDE THE EMERGENCY (OVERFLOW) STORM |
| | DRAINS ON THE STORM DRAIN RISER. SHOW THE PITCH OF THE |
| | HORIZONTAL DRAIN. |
| | 6) SHT. A401 - SHOW THE LOCATION OF THE ROOF DRAINS AND |
| | OVERFLOW DRAINS ON THE PLAN. |
| | 7) SHT. P202 - FLOOR DRAINS ARE SHOWN IN ROOMS #109, |
| | #190, #1191, #193, #233 & #290. THESE DRAINS ARE |
| | CONNECTED TO THE SANITARY AND WILL REQUIRE TRAP PRIMERS |
| | PER 2014 FPC SEC.1002.4. |
| | 8) SHT. P302 - THERE ARE STILL SECTIONS OF THE SANITARY |
| | SYSTEM (VENTS, BUILDING DRAIN,..) THAT ARE NOT SIZED. |
| | WPB AMEND. TO FBC SEC. 107.2.1. |
| | 9) SHT. A-761 - CLEARLY SHOW THE CONTROL WALL IN THE |
| | HANDICAPPED ACCESSIBLE TRANSFER SHOWERS. THE GRAPHICS |
| | ARE SO LIGHT THAT THE CONTROL WALL IS DIFFICULT TO |
| | DETERMINE. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 10) SUBMIT DETAILS FOR THE GENERATORS IN THE EQUIPMENT |
| | CORRAL. SUBMIT INFORMATION ON THE FUEL SOURCE FOR THE |
| | GENERATORS, PIPING DETAILS (IF APPLICABLE) ETC.WPB |
| | AMEND. TO FBC SEC. 107.2.1.2ND REQUEST.THE NARRATIVE |
| | REFERS TO THE ELECTRICAL PLANS FOR INFORMATION. I COULD |
| | NOT FIND ANY INFORMATION ON THE GENERATOR IN THE |
| | ELECTRICAL PLANS. CLARIFY. |
| | 11) SHT. A-701 - DETAIL 01- G6 ACCESSIBLE SHOWER - THE |
| | SHOWER CONTROLS, FAUCET AND SHOWER SPRAY UNIT IN THE |
| | ACCESSIBLE TRANSFER SHOWERS SHALL BE LOCATED ON THE |
| | SIDE WALL OPPOSITE THE SEAT 38 INCHES MINIMUM AND 48 |
| | INCHES MAXIMUM ABOVE THE SHOWER FLOOR AND SHALL BE |
| | LOCATED ON THE CONTRL WALL 15 INCHES MAXIMUM FROM THE |
| | CENTERLINE OF THE SEAT TOWARD THE SHOWER OPENING.2014 |
| | FAC SEC.608.5.1. THE DETAIL SHOWS THIS AS AN "OPTIONAL |
| | SHOWER HEAD AND CONTROL LOCATION." THIS IS NOT |
| | OPTIONAL. CLEARLY SHOW COMPLIANCE WITH THIS CODE |
| | SECTION. |
| | 12) GRAB BARS IN THE ACCESSIBLE TRANSFER SHOWERS SHALL |
| | COMPLY WITH 2014 FAC SEC.608.3.1. CLEARLY SHOW |
| | COMPLIANCE WITH THIS CODE SECTION ON THE PLANS. |
| | 13) NOTE: THE FINISHED CLEAR INSIDE DIMENSIONS OF THE |
| | ACCESSIBLE TRANSFER SHOWERS SHALL BE 36 INCHES BY 36 |
| | INCHES MEASURED AT THE CENTER POINTS OF OPPOSING SIDES. |
| | FINISHED DIMENSIONS OTHER THAN THIS IS NON-COMPLIANT. |
| | 14) SHT. P-201 - WHERE IS THE SANITARY LINE FOR ROOM |
| | #187? 2ND REQUEST. |
| | 15) CLEARLY SHOW THE LOCATION OF GRAB BARS IN THE |
| | HANDICAPPED ACCESSIBLE TRANSFER SHOWERS. COMPLY WITH |
| | 2015 FBC SEC.608.3.1 AND FIGURE 608.3.1. |
| | 15) THE FOLLOWING ITEMS WILL BE CONSIDERED DEFERRED |
| | SUBMITTALS. DOCUMENTATION SHALL BE SUBMITTED FOR REVIEW |
| | PRIOR TO WORK STARTING ON THESE ITEMS. |
| | |
| | 1) MANUFACTURER'S SPECIFICATIONS FOR THE WATER TANK. |
| | 2) MANUFACTURER'S SPECIFICATIONS FOR THE BLADDER TANK |
| | AND SIZE OF THE BLADDER TANK. |
| | 3) DETAILS AND DIMENSIONS FOR THE ANCHORING OF THE |
| | WATER TANK, SIZE AND TYPE OF STRAPS, TRAFFIC PROTECTION |
| | FOR THE PUMPS, SPECS ON THE PUMPS, ETC. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |