| Plan Review Notes For Permit 16090832 |
| Permit Number |
16090832 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-12-01 12:09:54 | 2ND ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 | | | PROVISO FOR NEW COMMENT: | | | | | | | | | 1. GFCI PROTECTION REQUIRED FOR ALL 15A-20A 125V | | | RECEPTACLES PER NEC 210.8B2 IN LOCKER AREA AND DRINKING | | | FOUNTAIN NEC 422.52 | | | | | | 1ST REVIEW COMMENT TO BE ADDRESSED: | | | 10. MAIN ELECTRICAL ROOMS MUST COMPLY WITH NEC | | | 110.26C2, THERE SHALL BE ONE ENTRANCE AT EACH END OF | | | THE WORKING SPACE. SHOW TWO MEANS OF EGRESS THAT | | | COMPLIES WITH EGRESS REQUIREMENTS, AS ONE OF THE DOOR | | | OPENS INTO A HAZARD AREA AND DOES NOT HAVE THE | | | CLEARANCE REQUIREMENTS. ALSO NEC 110.26C3 REQUIRES | | | PERSONNEL DOORS TO BE EQUIPPED WITH PANIC HARDWARE AND | | | OPEN IN THE DIRECTION OF EGRESS. DOOR MUST SWING IN THE | | | DIRECTION OF EGRESS. (TO COMPLY WITH NEC 110.26C3 | | | DOUBLE DOORS ADJACENT TO FACP MUST BE SHIFTED TO THE | | | RIGHT, LOCATION OF PANEL LDPA) | | | 11. PLEASE FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY | | | QUESTIONS REGARDING THIS PROJECT. | | | | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | | | | | | | | | | | | | | | | |
|