Plan Review Notes
Plan Review Notes For Permit 16090832
Permit Number 16090832
Review Stop E
Sequence Number 2
Notes
Date Text
2016-12-01 12:09:542ND ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 PROVISO FOR NEW COMMENT:
  
  
 1. GFCI PROTECTION REQUIRED FOR ALL 15A-20A 125V
 RECEPTACLES PER NEC 210.8B2 IN LOCKER AREA AND DRINKING
 FOUNTAIN NEC 422.52
  
 1ST REVIEW COMMENT TO BE ADDRESSED:
 10. MAIN ELECTRICAL ROOMS MUST COMPLY WITH NEC
 110.26C2, THERE SHALL BE ONE ENTRANCE AT EACH END OF
 THE WORKING SPACE. SHOW TWO MEANS OF EGRESS THAT
 COMPLIES WITH EGRESS REQUIREMENTS, AS ONE OF THE DOOR
 OPENS INTO A HAZARD AREA AND DOES NOT HAVE THE
 CLEARANCE REQUIREMENTS. ALSO NEC 110.26C3 REQUIRES
 PERSONNEL DOORS TO BE EQUIPPED WITH PANIC HARDWARE AND
 OPEN IN THE DIRECTION OF EGRESS. DOOR MUST SWING IN THE
 DIRECTION OF EGRESS. (TO COMPLY WITH NEC 110.26C3
 DOUBLE DOORS ADJACENT TO FACP MUST BE SHIFTED TO THE
 RIGHT, LOCATION OF PANEL LDPA)
 11. PLEASE FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS REGARDING THIS PROJECT.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  
  
  
  