| 2016-10-21 14:44:52 | 1) PROVIDE A SECTION DETAIL OF THE 2 SANITARY HOLDING |
| | TANKS SHOWING THE CONSTRUCTION OF THE TANK IN DETAIL. |
| | ARE THEY DESIGNED AS SEPTIC TANKS ON THE INTERIOR? |
| | CLARIFY.WPB AMEND. TO FBC SEC. 107.2.1. |
| | 2) SUBMIT A BRIEF NARRATIVE AS TO THE |
| | OPERATION/SEQUENCING OF THE TANKS WHEN THEY ARE PUT |
| | INTO OPERATION. AS PIPED, IT IS CONFUSING TO DETERMINE |
| | HOW THEY WILL WORK.WPB AMEND. TO FBC SEC. 107.2.1. |
| | 3) A GREASE INTERCEPTOR IS REQUIRED FOR THE KITCHEN PER |
| | THE 2014 FBC- PLUMBING, SEC.1003.1, 1003.3.1. |
| | 4) SUBMIT SIZING CALCULATIONS FOR THE GREASE |
| | INTERCEPTOR.THE SIZE, TYPE AND LOCATION OF EACH |
| | INTERCEPTOR SHALL BE APPROVED BY THE PLUMBING OFFICIAL. |
| | FPC SEC.1003.2. |
| | 5) THE BREAKROOM SINK & COUNTER SHALL COMPLY WITH 2014 |
| | FBC-ACCESSIBILITY SECS.212, 606.SEE SHT. A-741. |
| | 6) 2ND FLOOR RESTROOM # 280 REQUIRES AN ACCCESSIBLE |
| | AMBULATORY COMPARTMENT THAT COMPLIES WITH FAC |
| | SEC.213.3.1 & SEC.604.8.2 PER 2014 FBC-ACCESS. |
| | 7) SHT. A401 - THE STORM DRAINAGE TABLE ON THIS SHEET |
| | DOES NOT SEEM TO INCLUDE ONE-HALF THE AREA OF VERTICAL |
| | WALLS THAT CAN DIVERT RAINWATER TO THE ROOF. SEE 2014 |
| | FPC SEC.1106.4. |
| | 8) SHT. A 401 - THE CODED NOTES REFER TO SHTS. A-450 |
| | AND A-451 FOR SCUPPER AND ROOF DRAIN DETAILS AND THERE |
| | IS NO ROOF DRAIN DETAIL ON A-450. MOST OF THE DETAILS |
| | ARE ON SHT. A- 452 .PLEASE REVISE THE NOTES. ALSO, THE |
| | PLANS SHOW ROOF DRAIN DETAILS BUT THERE ARE SCUPPERS |
| | SHOWN ON THE PLANS.CLARIFY. |
| | 9) SHT.A-760 - THE GRAB BARS SHALL BE MEASURED FROM |
| | FINISH FLOOR TO THE TOP OF THE GRIPPING SURFACE. FAC |
| | SEC.609.4. |
| | 10) SHT. A-761 - SHOW THE CLEAR INSIDE DIMENSIONS OF |
| | THE STANDARD AND HANDICAPPED ACCESSIBLE SHOWERS ON SHT. |
| | A-761 |
| | 11) AT LEAST ONE LAVATORY IN THE RESTROOMS SHAL COMPLY |
| | WITH 2014 FAC SEC.606 AND SHALL NOT BE LOCATED IN A |
| | TOILET COMPARTMENT. FAC SEC.213.3.4. |
| | 12) RESTROOMS #183 & 184 SHALL CONTAIN A HANDICAPPED |
| | ACCESSIBLE TOILET COMPARTMENT WITHIN EACH RESTROOM. |
| | 2014 FAC SEC. 213.3.1. |
| | 13) WHERE MORE THAN ONE URINAL IS PROVIDED, AT LEAST |
| | ONE SHALL COMPLY WITH FAC SEC. 605. IDENTIFY THE |
| | HANDICAPPED URINALS IN THE RESTROOMS AND SHOW |
| | COMPLIANCE W/ FAC SEC. 605. |
| | 14) SHT. LS-201 - THE FITNESS ROOM IS CALCULATED AT 100 |
| | SQUARE FEET PER PERSON BUT SHOULD BE CALCULATED AT 50 |
| | SQUARE FEET PER PERSON PER 2014 FBC TABLE 1004.1.2. |
| | 15) SHT. LS-100 - PROJECT SUMMARY DOES NOT INCLUDE THE |
| | STORAGE OCCUPANCY OR THE SQUARE FOOTAGE. CLARIFY. |
| | 16) SHT.P201 - WHERE IS THE SANITARY LINE FOR ROOM |
| | #187? |
| | 17) THE KITCHEN (ROOM #124) WASTE SHALL DISCHARGE |
| | THROUGH A GREASE INTERCEPTOR PER 2014 FPC SEC.1003.3.1. |
| | 18) SUBMIT A CONDENSATE RISER DIAGRAM FOR REVIEW. WPB |
| | AMEND. TO FBC SEC. 107.2.1, 107.3.5.1.3. |
| | 19) SUBMIT A STORM WATER RISER IF ROOF DRAINS ARE GOING |
| | TO BE INSTALLED. WPB AMEND. TO FBC SEC.107.2.1.THE |
| | STRUCTURE SHALL BE PROVIDED WITH EMERGENCY (OVERFLOW) |
| | ROOF DRAINS OR SCUPPERS PER FPC SEC. 1108. |
| | 20) SHT. P202 - FLOOR DRAINS ARE SHOWN IN ROOMS #109, |
| | #190, #191, #193, #233, & # 290.WHAT WILL BE |
| | DISCHARGING INTO THESE FLOOR DRAINS? CONDENSATE WASTE |
| | SHALL NOT DISCHARGE INTO THE SANITARY SYSTEM PER CITY |
| | OF WPB CODE OF ORDINANCES CHAPT. 90, ART. III, SEC. |
| | 90-126 (B) (5). TRAP PRIMERS MAY BE REQUIRED ON THESE |
| | FLOOR DRAINS PER FPC SEC.1002.4. |
| | 21) SHT. P-222 - THE PLAN SHOWS A 3 INCH WASTE & 3 INCH |
| | CONDENSATE DRAIN DOWN IN CORRIDOR #026. CLARIFY. |
| | 22) SHT.P-301 - THE MOP SINK IN ROOM #230 IS NOT DHOWN |
| | ON THE SANITARY OR WATER RISER DIAGRAMS. CLARIFY. |
| | 23) SHT. P-302 - SIZE ALL VENTS, STACKS, ALL WET |
| | SECTIONS OF THE WASTE STACKS, & ALL SECTIONS OF THE |
| | BUILDING DRAIN. WPB AMEND. TO FBC SEC.107.2.1. |
| | 24) SHT. P-302 - PLEASE IDENTIFY THE RISERS ON SHTS. |
| | P-302 & P-303 AS TO THEIR SPECIFIC AREAS IN THE |
| | BUILDING. THIS WILL HELP EXPEDITE THE RE-REVIEW. WPB |
| | AMEND. TO FBC SEC. 107.2.1. |
| | 25) SIZE THE WATER RISERS IN THEIR ENTIRETY. LABEL THE |
| | RISERS TO CORRELATE WITH THEIR LOCATION ON THE FLOOR |
| | PLAN.WPB AMEND. TO FBC SEC. 107.2.1. |
| | 25) SUBMIT A COMPLETE WATER RISER FOR REVIEW THAT |
| | BEGINS AT THE SOURCE TO THE END POINT. WPB AMEND. TO |
| | FBC SEC. 107.2.1, 107.3.5.1.3.3. |
| | 26) SUBMIT A COMPLETE SANITARY RISER DIAGRAM FOR |
| | REVIEW. THE RISER SHALL INCLUDE THE COMPLETE |
| | UNDERGROUND SYSTEM AND ALL BRANCHES FROM THE POINT |
| | WHERE THE BUILDING DRAIN EXITS THE BUILDING TO THE END |
| | POINT.WPB AMEND. TO FBC SEC. 107.2.1, 107.3.5.1.3.3. |
| | 27) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE WATER |
| | TANK. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 28) SUBMIT DETAILS/ MANUF. SPECIFICATIONS FOR THE |
| | BLADDER TANK AND INDICATE THE SIZE OF THE BLADDER TANK |
| | ON SHT. P-402. |
| | 29) SUBMIT DETAILS AND DIMENSIONS OF THE ANCHOR PAD FOR |
| | THE WATER TANK.SUPPLY INFORMATION FOR THE ANCHORING OF |
| | THE TANK, SIZE AND TYPE OF STRAPS, TRAFFIC PROTECTION |
| | FOR THE PUMPS, ANCHORING DETAILS FOR THE WATER TANK ( |
| | TYPE, LENGTH OF FASTENERS, ETC.) |
| | 30) SHT. P-402 - WATER HEATER DETAIL "A" - THE HOT |
| | WATER/ TEMPERED WATER RETURN LINE SHALL BE ROUTED TO |
| | THE COLD WATER INLET PIPE OF THE HOT WATER HEATER AND |
| | THE COLD WATER INLET PIPE OR THE HOT WATER RETURN |
| | CONNECTION OF THE THERMOSTATIC MIXING VALVE 2014 FPC |
| | SEC.607.2.2. |
| | 31) THERE SHALL BE A BACKFLOW PREVENTER INSTALLED ON |
| | THE WATER SUPPLY TO THE WATER TANK. 2014 FPC SEC. |
| | 608.12, 608.13. |
| | 31) SUBMIT DETAILS FOR THE GENERATORS IN THE EQUIPMENT |
| | CORRAL. SUBMIT INFORMATION ON THE FUEL SOURCE FOR THE |
| | GENERATORS, PIPING DETAILS ( IF APPLICABLE), ETC.WPB |
| | AMEND. TO FBC SEC. 107.2.1. |
| | 32) INDICATE ON THE PLAN IF ANY LP OR NATURAL GAS WILL |
| | BE INSTALLED FOR THIS PROJECT. IF SO, SUBMIT COMPLETE |
| | DETAILS ON THE SYSTEM ( PIPING RISER, TYPE OF FUEL, |
| | LOCATION OF METER OR TANK), ETC. |
| | 33) A CLEAR FLOOR SPACE OF 30 INCHES WIDE MINIMUM BY 48 |
| | INCHES LONG MINIMUM MEASURED FROM THE CONTROL WALL |
| | SHALL BE PROVIDED FOR THE HANDICAPPED ACCESSIBLE |
| | TRANSFER SHOWERS PER 2014 FAC SEC.608.2.1. |
| | 34) THE TRANSFER SHOWERS SHALL BE 36 INCHES BY 36 |
| | INCHES CLEAR INSIDE DIMENSIONS MEASURED AT THE CENTER |
| | POINTS OF OPPOSING SIDES.2014 FAC SEC.608.2.1. |
| | 35) THE SHOWER CONTROLS, FAUCET AND SHOWER SPRAY UNIT |
| | IN THE ACCESSIBLE SHOWERS SHALL BE LOCATED ON THE SIDE |
| | WALL OPPOSITE THE SEAT 38 INCHES MINIMUM AND 48 INCHES |
| | MAXIMUM ABOVE THE SHOWER FLOOR AND SHALL BE LOCATED ON |
| | THE CONTROL WALL 15 INCHES MAXIMUM FROM THE CENTERLINE |
| | OF THE SEAT TOWARD THE SHOWER OPENING.2014 FAC |
| | SEC.608.5.1. |
| | 36) GRAB BARS IN THE ACCESSIBLE TRANSFER SHOWERS SHALL |
| | COMPLY WITH 2014 FAC SEC.608.3.1. |
| | 37) THE COUNTER IN THE BREAK ROMM SHALL BE A MAXIMUM OF |
| | 34 INCHES FROM THE FINISH FLOOR TO THE TOP OF THE |
| | COUNTER PER 2014 FAC SEC. 212 & 606. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |