Plan Review Notes
Plan Review Notes For Permit 16090832
Permit Number 16090832
Review Stop P
Sequence Number 1
Notes
Date Text
2016-10-21 14:44:521) PROVIDE A SECTION DETAIL OF THE 2 SANITARY HOLDING
 TANKS SHOWING THE CONSTRUCTION OF THE TANK IN DETAIL.
 ARE THEY DESIGNED AS SEPTIC TANKS ON THE INTERIOR?
 CLARIFY.WPB AMEND. TO FBC SEC. 107.2.1.
 2) SUBMIT A BRIEF NARRATIVE AS TO THE
 OPERATION/SEQUENCING OF THE TANKS WHEN THEY ARE PUT
 INTO OPERATION. AS PIPED, IT IS CONFUSING TO DETERMINE
 HOW THEY WILL WORK.WPB AMEND. TO FBC SEC. 107.2.1.
 3) A GREASE INTERCEPTOR IS REQUIRED FOR THE KITCHEN PER
 THE 2014 FBC- PLUMBING, SEC.1003.1, 1003.3.1.
 4) SUBMIT SIZING CALCULATIONS FOR THE GREASE
 INTERCEPTOR.THE SIZE, TYPE AND LOCATION OF EACH
 INTERCEPTOR SHALL BE APPROVED BY THE PLUMBING OFFICIAL.
 FPC SEC.1003.2.
 5) THE BREAKROOM SINK & COUNTER SHALL COMPLY WITH 2014
 FBC-ACCESSIBILITY SECS.212, 606.SEE SHT. A-741.
 6) 2ND FLOOR RESTROOM # 280 REQUIRES AN ACCCESSIBLE
 AMBULATORY COMPARTMENT THAT COMPLIES WITH FAC
 SEC.213.3.1 & SEC.604.8.2 PER 2014 FBC-ACCESS.
 7) SHT. A401 - THE STORM DRAINAGE TABLE ON THIS SHEET
 DOES NOT SEEM TO INCLUDE ONE-HALF THE AREA OF VERTICAL
 WALLS THAT CAN DIVERT RAINWATER TO THE ROOF. SEE 2014
 FPC SEC.1106.4.
 8) SHT. A 401 - THE CODED NOTES REFER TO SHTS. A-450
 AND A-451 FOR SCUPPER AND ROOF DRAIN DETAILS AND THERE
 IS NO ROOF DRAIN DETAIL ON A-450. MOST OF THE DETAILS
 ARE ON SHT. A- 452 .PLEASE REVISE THE NOTES. ALSO, THE
 PLANS SHOW ROOF DRAIN DETAILS BUT THERE ARE SCUPPERS
 SHOWN ON THE PLANS.CLARIFY.
 9) SHT.A-760 - THE GRAB BARS SHALL BE MEASURED FROM
 FINISH FLOOR TO THE TOP OF THE GRIPPING SURFACE. FAC
 SEC.609.4.
 10) SHT. A-761 - SHOW THE CLEAR INSIDE DIMENSIONS OF
 THE STANDARD AND HANDICAPPED ACCESSIBLE SHOWERS ON SHT.
 A-761
 11) AT LEAST ONE LAVATORY IN THE RESTROOMS SHAL COMPLY
 WITH 2014 FAC SEC.606 AND SHALL NOT BE LOCATED IN A
 TOILET COMPARTMENT. FAC SEC.213.3.4.
 12) RESTROOMS #183 & 184 SHALL CONTAIN A HANDICAPPED
 ACCESSIBLE TOILET COMPARTMENT WITHIN EACH RESTROOM.
 2014 FAC SEC. 213.3.1.
 13) WHERE MORE THAN ONE URINAL IS PROVIDED, AT LEAST
 ONE SHALL COMPLY WITH FAC SEC. 605. IDENTIFY THE
 HANDICAPPED URINALS IN THE RESTROOMS AND SHOW
 COMPLIANCE W/ FAC SEC. 605.
 14) SHT. LS-201 - THE FITNESS ROOM IS CALCULATED AT 100
 SQUARE FEET PER PERSON BUT SHOULD BE CALCULATED AT 50
 SQUARE FEET PER PERSON PER 2014 FBC TABLE 1004.1.2.
 15) SHT. LS-100 - PROJECT SUMMARY DOES NOT INCLUDE THE
 STORAGE OCCUPANCY OR THE SQUARE FOOTAGE. CLARIFY.
 16) SHT.P201 - WHERE IS THE SANITARY LINE FOR ROOM
 #187?
 17) THE KITCHEN (ROOM #124) WASTE SHALL DISCHARGE
 THROUGH A GREASE INTERCEPTOR PER 2014 FPC SEC.1003.3.1.
 18) SUBMIT A CONDENSATE RISER DIAGRAM FOR REVIEW. WPB
 AMEND. TO FBC SEC. 107.2.1, 107.3.5.1.3.
 19) SUBMIT A STORM WATER RISER IF ROOF DRAINS ARE GOING
 TO BE INSTALLED. WPB AMEND. TO FBC SEC.107.2.1.THE
 STRUCTURE SHALL BE PROVIDED WITH EMERGENCY (OVERFLOW)
 ROOF DRAINS OR SCUPPERS PER FPC SEC. 1108.
 20) SHT. P202 - FLOOR DRAINS ARE SHOWN IN ROOMS #109,
 #190, #191, #193, #233, & # 290.WHAT WILL BE
 DISCHARGING INTO THESE FLOOR DRAINS? CONDENSATE WASTE
 SHALL NOT DISCHARGE INTO THE SANITARY SYSTEM PER CITY
 OF WPB CODE OF ORDINANCES CHAPT. 90, ART. III, SEC.
 90-126 (B) (5). TRAP PRIMERS MAY BE REQUIRED ON THESE
 FLOOR DRAINS PER FPC SEC.1002.4.
 21) SHT. P-222 - THE PLAN SHOWS A 3 INCH WASTE & 3 INCH
 CONDENSATE DRAIN DOWN IN CORRIDOR #026. CLARIFY.
 22) SHT.P-301 - THE MOP SINK IN ROOM #230 IS NOT DHOWN
 ON THE SANITARY OR WATER RISER DIAGRAMS. CLARIFY.
 23) SHT. P-302 - SIZE ALL VENTS, STACKS, ALL WET
 SECTIONS OF THE WASTE STACKS, & ALL SECTIONS OF THE
 BUILDING DRAIN. WPB AMEND. TO FBC SEC.107.2.1.
 24) SHT. P-302 - PLEASE IDENTIFY THE RISERS ON SHTS.
 P-302 & P-303 AS TO THEIR SPECIFIC AREAS IN THE
 BUILDING. THIS WILL HELP EXPEDITE THE RE-REVIEW. WPB
 AMEND. TO FBC SEC. 107.2.1.
 25) SIZE THE WATER RISERS IN THEIR ENTIRETY. LABEL THE
 RISERS TO CORRELATE WITH THEIR LOCATION ON THE FLOOR
 PLAN.WPB AMEND. TO FBC SEC. 107.2.1.
 25) SUBMIT A COMPLETE WATER RISER FOR REVIEW THAT
 BEGINS AT THE SOURCE TO THE END POINT. WPB AMEND. TO
 FBC SEC. 107.2.1, 107.3.5.1.3.3.
 26) SUBMIT A COMPLETE SANITARY RISER DIAGRAM FOR
 REVIEW. THE RISER SHALL INCLUDE THE COMPLETE
 UNDERGROUND SYSTEM AND ALL BRANCHES FROM THE POINT
 WHERE THE BUILDING DRAIN EXITS THE BUILDING TO THE END
 POINT.WPB AMEND. TO FBC SEC. 107.2.1, 107.3.5.1.3.3.
 27) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE WATER
 TANK. WPB AMEND. TO FBC SEC. 107.2.1.
 28) SUBMIT DETAILS/ MANUF. SPECIFICATIONS FOR THE
 BLADDER TANK AND INDICATE THE SIZE OF THE BLADDER TANK
 ON SHT. P-402.
 29) SUBMIT DETAILS AND DIMENSIONS OF THE ANCHOR PAD FOR
 THE WATER TANK.SUPPLY INFORMATION FOR THE ANCHORING OF
 THE TANK, SIZE AND TYPE OF STRAPS, TRAFFIC PROTECTION
 FOR THE PUMPS, ANCHORING DETAILS FOR THE WATER TANK (
 TYPE, LENGTH OF FASTENERS, ETC.)
 30) SHT. P-402 - WATER HEATER DETAIL "A" - THE HOT
 WATER/ TEMPERED WATER RETURN LINE SHALL BE ROUTED TO
 THE COLD WATER INLET PIPE OF THE HOT WATER HEATER AND
 THE COLD WATER INLET PIPE OR THE HOT WATER RETURN
 CONNECTION OF THE THERMOSTATIC MIXING VALVE 2014 FPC
 SEC.607.2.2.
 31) THERE SHALL BE A BACKFLOW PREVENTER INSTALLED ON
 THE WATER SUPPLY TO THE WATER TANK. 2014 FPC SEC.
 608.12, 608.13.
 31) SUBMIT DETAILS FOR THE GENERATORS IN THE EQUIPMENT
 CORRAL. SUBMIT INFORMATION ON THE FUEL SOURCE FOR THE
 GENERATORS, PIPING DETAILS ( IF APPLICABLE), ETC.WPB
 AMEND. TO FBC SEC. 107.2.1.
 32) INDICATE ON THE PLAN IF ANY LP OR NATURAL GAS WILL
 BE INSTALLED FOR THIS PROJECT. IF SO, SUBMIT COMPLETE
 DETAILS ON THE SYSTEM ( PIPING RISER, TYPE OF FUEL,
 LOCATION OF METER OR TANK), ETC.
 33) A CLEAR FLOOR SPACE OF 30 INCHES WIDE MINIMUM BY 48
 INCHES LONG MINIMUM MEASURED FROM THE CONTROL WALL
 SHALL BE PROVIDED FOR THE HANDICAPPED ACCESSIBLE
 TRANSFER SHOWERS PER 2014 FAC SEC.608.2.1.
 34) THE TRANSFER SHOWERS SHALL BE 36 INCHES BY 36
 INCHES CLEAR INSIDE DIMENSIONS MEASURED AT THE CENTER
 POINTS OF OPPOSING SIDES.2014 FAC SEC.608.2.1.
 35) THE SHOWER CONTROLS, FAUCET AND SHOWER SPRAY UNIT
 IN THE ACCESSIBLE SHOWERS SHALL BE LOCATED ON THE SIDE
 WALL OPPOSITE THE SEAT 38 INCHES MINIMUM AND 48 INCHES
 MAXIMUM ABOVE THE SHOWER FLOOR AND SHALL BE LOCATED ON
 THE CONTROL WALL 15 INCHES MAXIMUM FROM THE CENTERLINE
 OF THE SEAT TOWARD THE SHOWER OPENING.2014 FAC
 SEC.608.5.1.
 36) GRAB BARS IN THE ACCESSIBLE TRANSFER SHOWERS SHALL
 COMPLY WITH 2014 FAC SEC.608.3.1.
 37) THE COUNTER IN THE BREAK ROMM SHALL BE A MAXIMUM OF
 34 INCHES FROM THE FINISH FLOOR TO THE TOP OF THE
 COUNTER PER 2014 FAC SEC. 212 & 606.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW