2016-09-29 17:02:241ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16090832
 9/29/16
  
 1) PROVIDE VENTILATION CALCULATIONS FOR O/A AND EXHAUST
 FOR ALL ROOMS AND SPACES USING THE DESIGN PARAMETERS
 SHOWN IN TABLE 403.3 FBC-14 MECHANICAL. PROVIDE A
 SCHEDULE INDICATING THE REQUIRED AND PROVIDED CFMS OF
 O/A AND EXHAUST. THE DESIGN CRITERIA TABLE ON M-101
 DOES NOT APPEAR TO BE CONSISTENT WITH TABLE 403.3, AND
 DOES NOT SHOW ANY EXHAUST CALCULATIONS.
  
 2) DESIGN EFFICIENCIES AND CRITERIA FOR THE AHU'S ARE
 NOT LISTED IN THE ENERGYGAUGE SUBMITTAL OR IN THE AHU
 SCHEDULE ON SHEET M-102.
  
 3) THE ENERGYGAUGE SUBMITTAL SHOWS COMPLIANCE DATA FOR
 CRU'S 12, 34, & 56, HOWEVER THE SCHEDULE INDICATES
 CRU'S 1, 2, 3, 4, 5, & 6.
  
 4) PROVIDE PIPING SYSTEM COMPLIANCE DATA IN THE
 ENERGYGAUGE SUBMITTAL.
  
 5) THE AC CALCULATIONS AND SCHEDULE FOR THE COMPUTER
 SYSTEMS DO NOT MATCH IN SYSTEM IDENTIFICATIONS, NUMBER
 OF SYSTEMS, AND CAPACITIES OF SYSTEMS.
  
 6) THE HEATING CAPACITIES OF THE AHU-3 TERMINAL BOXES
 ARE EXCEEDING THE CALCULATED HEATING COIL LOADS.
  
 7) M-103: PLEASE PROVIDE THE CHILLED WATER DATA IN THE
 CHILLER SCHEDULE.
  
 8) SHEET M-104: PROVIDE AN EQUIPMENT SCHEDULE FOR THE
 TEMPORARY AIR HANDLER AND INDICATE HOW THE DUCTWORK
 WILL BE SUPPORTED, PROTECTED, AND SEALED AT THE
 BUILDING PENETRATION
  
 9) M-201 & M-202: THE TEMPORARY AC SYSTEMS ARE LISTED
 AS BOTH AC-TEMP AND RTU-TEMP- PLEASE CLARIFY. INDICATE
 HOW THE AC EQUIPMENT WILL BE MOUNTED (EQUIPMENT IS NOT
 SHOWN ON A TRAILER) AND HOW THE DUCTWORK WILL BE
 SUPPORTED, PROTECTED, AND SEALED AT THE PENETRATION OF
 THE BUILDING. A) PLEASE NOTE THAT A GAS PIPING PLAN AND
 ISOMETRIC WILL BE REQUIRED FOR THE HEAT.
  
 10) M-211: FIRE DAMPERS, OR SYMBOLS FOR FIRE DAMPERS,
 APPEAR TO BE MISSING AT THE DUCT PENETRATIONS ALONG THE
 EAST WALL OF THE CONTROL THEATER- SECTION 607.5.2.
  
 11) M-211: PLEASE CLARIFY THE PURPOSE OF EF-1-1 &
 EF-2-1 AND HOW THESE FANS WERE SIZED.
  
 12) M-212: SEE COMMENT #9 CONCERNING MISSING FIRE
 DAMPERS FOR DUCTS PENETRATING THE FIRE-RATED WALL. IT
 APPEARS THAT MANY OTHER DAMPERS ARE MISSING WHERE DUCTS
 PENETRATE FIRE-RATED CORRIDOR AND OTHER SEPARATION
 WALLS. PLEASE OVERLAY THE LIFE SAFETY PLANS ON THE
 MECHANICAL LAYOUT PAGES SO THAT RATED WALLS ARE CLEARLY
 SHOWN.
  
 13) M-212: EF 4-1 AND TG-1 ARE UNDERSIZED FOR THE
 MINIMUM REQUIRED EXHAUST CFMS FROM THE MENS RESTROOM
 180 PER TABLE 403.3- 250 CFMS.
  
 14) M-212: PROVIDE AN EXHAUST VENTILATION CALCULATION
 FOR THE LOCKER ROOM- TABLE 403.3.
  
 15) M-211- M222: PLEASE LABEL OR TAG ALL TB ACCESS
 PANELS, AND PROVIDE ACCESS TO ABOVE CEILING EXHAUST
 FANS- SECTION 306.1.
  
 16) PROVIDE CHILLED WATER PIPING DETAILS- TYPE OF
 PIPING, JOINERY, INSULATION.
  
 17) PROVIDE ENGINEERED STRUCTURAL DETAILS AND THE WIND
 LOAD DESIGN CRITERIA FOR INSTALLATION OF THE CHILLERS
 AND THE PUMPS- SECTION 301.15.
  
 18) SUBMIT FL. PRODUCT APPROVALS AND/OR MIAMI-DADE
 NOA'S FOR ALL AIR INTAKE AND EXHAUST LOUVERS.
  