Plan Review Notes
Plan Review Notes For Permit 16090832
Permit Number 16090832
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2016-09-30 16:12:10THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET C 8 - THE PROPOSED INDICATED FDC CONFIGURATION
 IS NOT COMPLIANT. THE FDC SHAL NOT BE IN A POSITION TO
 PROVIDE PRESSURE TO THE FIRE LINE SUPPLY SYSTEM.
  
  
 PER NFPA 13
  
 8.17.2.4* ARRANGEMENT. SEE FIGURE 8.17.2.1.
 8.17.2.4.1* THE FIRE DEPARTMENT CONNECTION SHALL BE ON
 THESYSTEM SIDE OF THE WATER SUPPLY CHECK VALVE.
  
 8.17.2.4.2 FOR SINGLE SYSTEMS, THE FIRE DEPARTMENT
 CONNECTION SHALL BE INSTALLED AS FOLLOWS:
 (1) WET SYSTEM?ON THE SYSTEM SIDE OF SYSTEM CONTROL,
 CHECK, AND ALARM VALVES (SEE FIGURE A.8.16.1.1)
  
  
 A.8.17.2.4 THE CHECK VALVE SHOULD BE LOCATED TO
 MAXIMIZE ACCESSIBILITY AND MINIMIZE FREEZING POTENTIAL.
 IT IS RECOMMENDED THAT THE CHECK VALVE BE LOCATED TO
 REDUCE THE LENGTH OF NONPRESSURIZED PIPE IN THE FIRE
 DEPARTMENT CONNECTION SUPPLY LINE.
 A.8.17.2.4.1 THE FIRE DEPARTMENT CONNECTION SHOULD BE
 CONNECTED TO THE SYSTEM RISER. FOR SINGLE SYSTEMS, IT
 IS AN ACCEPTABLE ARRANGEMENT TO ATTACH THE FIRE
 DEPARTMENT CONNECTION TO ANY POINT IN THE SYSTEM,
 PROVIDED THE PIPE SIZE MEETS THE REQUIREMENTS OF
 8.17.2.3.
  
  
 2) SHEET C 8 - THE LOCATION OF THE FDC AND HYDRANT IS
 RECOMENDED TO BE PLACED CLOSER TO THE BUILDING, OR THE
 FDC ATTACHED TO THE BUILDING, CLOSER TO THE AREA OF FD
 ACCESS. THIS WAS PREVIOUSLY STATED DURING PPRC
 COMMENTS.
  
  
 3) SHEET LS 100 - THERE ARE INCORRECT REFERENCES AND
 EDITIONS TO THE FIRE CODES.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2010 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION.
 CLEAN AGENT SYSTEMS SHALL COMPLY WITH NFPA 2001, 2012
 EDITION.
 EMERGENCY AND STANDBY POWER SYSTEMS SHALL COMPLY WITH
 NFPA 110, 2013 EDITION.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  