| 2016-10-11 09:01:22 | INITIAL ELECTRICAL PLAN REVIEW |
| | |
| | APPLICABLE CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70- 2011 |
| | COMMENTS: |
| | |
| | 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE |
| | PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE |
| | PERMITS AND DATA CUT SHEET SUBMITTALS FOR ALL SITE |
| | LIGHTING AND ASSOCIATED EQUIPMENT, GENERATOR, ALL LOW |
| | VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE |
| | ALARM, ACCESS CONTROLS, CCTV, PHONE AND DATA, WIRELESS |
| | SYSTEMS, HOOD SYSTEMS, LIGHTNING PROTECTION GENERATORS, |
| | ETC. A NOTE WILL SUFFICE. |
| | 2. ADD A NOTE TO MAINTAIN ALL ELECTRICAL EQUIPMENT |
| | ABOVE THE BASELINE FLOOD ELEVATION PER STATE AND CITY |
| | REGULATORY AGENCIES. |
| | 3. GFCI PROTECTION REQUIRED FOR ALL 15A-20A 125V |
| | RECEPTACLES PER NEC 210.8B2 IN KITCHEN AREA. |
| | 4. RISER DIAGRAM AND PANEL SCHEDULES- PLEASE PROVIDE |
| | AVAILABLE FAULT CURRENT AVAILABLE AT THE FPL SERVICE. |
| | ATTACH TO DOCUMENTS LETTER FROM FLORIDA POWER & LIGHT |
| | INDICATING AIC. SHOW AIC CALCULATION BASED ON |
| | INFORMATION PROVIDED BY UTILITY FOR APPROVAL. NEC |
| | 110.24 FBC 107 |
| | 5. PLEASE ADD A NOTE TO ONE-LINE SHEET TO REFLECT THE |
| | REQUIREMENTS OF NEC 700.7A FOR SIGNAGE |
| | 6. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO |
| | INDICATE NEC 110.16. ARC FLASH WARNING SIGNS AND NEC |
| | 110.24- AVAILABLE FAULT CURRENT- FIELD MARKINGS; SEE |
| | VERBIAGE IN CODE. |
| | 7. PLEASE LABEL ATS?S ON ONE-LINE TO BE SEPARATELY |
| | DERIVED SYSTEM AS SHOWN ON DETAIL SHEET. |
| | 8. CLARIFY NOTE K ON RISER DIAGRAM, IF THESE ARE THE |
| | INTERLOCKS PLEASE ADD AS NOTE TO PLANS. |
| | 9. PROVIDE VOLTAGE DROP CALCULATIONS NOT ONLY FOR |
| | FEEDERS BUT ALSO THE BRANCH CIRCUIT FBC EC 505.7 |
| | 10. MAIN ELECTRICAL ROOMS MUST COMPLY WITH NEC |
| | 110.26C2, THERE SHALL BE ONE ENTRANCE AT EACH END OF |
| | THE WORKING SPACE. SHOW TWO MEANS OF EGRESS THAT |
| | COMPLIES WITH EGRESS REQUIREMENTS, AS ONE OF THE DOOR |
| | OPENS INTO A HAZARD AREA AND DOES NOT HAVE THE |
| | CLEARANCE REQUIREMENTS. ALSO NEC 110.26C3 REQUIRES |
| | PERSONNEL DOORS TO BE EQUIPPED WITH PANIC HARDWARE AND |
| | OPEN IN THE DIRECTION OF EGRESS. DOOR MUST SWING IN THE |
| | DIRECTION OF EGRESS. |
| | 11. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL |
| | FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS |
| | REGARDING THIS PROJECT. |
| | |
| | |
| | VALENTINO PEREZ |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6717 |