2016-10-11 09:01:22INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE
 PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE
 PERMITS AND DATA CUT SHEET SUBMITTALS FOR ALL SITE
 LIGHTING AND ASSOCIATED EQUIPMENT, GENERATOR, ALL LOW
 VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE
 ALARM, ACCESS CONTROLS, CCTV, PHONE AND DATA, WIRELESS
 SYSTEMS, HOOD SYSTEMS, LIGHTNING PROTECTION GENERATORS,
 ETC. A NOTE WILL SUFFICE.
 2. ADD A NOTE TO MAINTAIN ALL ELECTRICAL EQUIPMENT
 ABOVE THE BASELINE FLOOD ELEVATION PER STATE AND CITY
 REGULATORY AGENCIES.
 3. GFCI PROTECTION REQUIRED FOR ALL 15A-20A 125V
 RECEPTACLES PER NEC 210.8B2 IN KITCHEN AREA.
 4. RISER DIAGRAM AND PANEL SCHEDULES- PLEASE PROVIDE
 AVAILABLE FAULT CURRENT AVAILABLE AT THE FPL SERVICE.
 ATTACH TO DOCUMENTS LETTER FROM FLORIDA POWER & LIGHT
 INDICATING AIC. SHOW AIC CALCULATION BASED ON
 INFORMATION PROVIDED BY UTILITY FOR APPROVAL. NEC
 110.24 FBC 107
 5. PLEASE ADD A NOTE TO ONE-LINE SHEET TO REFLECT THE
 REQUIREMENTS OF NEC 700.7A FOR SIGNAGE
 6. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO
 INDICATE NEC 110.16. ARC FLASH WARNING SIGNS AND NEC
 110.24- AVAILABLE FAULT CURRENT- FIELD MARKINGS; SEE
 VERBIAGE IN CODE.
 7. PLEASE LABEL ATS?S ON ONE-LINE TO BE SEPARATELY
 DERIVED SYSTEM AS SHOWN ON DETAIL SHEET.
 8. CLARIFY NOTE K ON RISER DIAGRAM, IF THESE ARE THE
 INTERLOCKS PLEASE ADD AS NOTE TO PLANS.
 9. PROVIDE VOLTAGE DROP CALCULATIONS NOT ONLY FOR
 FEEDERS BUT ALSO THE BRANCH CIRCUIT FBC EC 505.7
 10. MAIN ELECTRICAL ROOMS MUST COMPLY WITH NEC
 110.26C2, THERE SHALL BE ONE ENTRANCE AT EACH END OF
 THE WORKING SPACE. SHOW TWO MEANS OF EGRESS THAT
 COMPLIES WITH EGRESS REQUIREMENTS, AS ONE OF THE DOOR
 OPENS INTO A HAZARD AREA AND DOES NOT HAVE THE
 CLEARANCE REQUIREMENTS. ALSO NEC 110.26C3 REQUIRES
 PERSONNEL DOORS TO BE EQUIPPED WITH PANIC HARDWARE AND
 OPEN IN THE DIRECTION OF EGRESS. DOOR MUST SWING IN THE
 DIRECTION OF EGRESS.
 11. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL
 FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS
 REGARDING THIS PROJECT.
  
  