Plan Review Notes
Plan Review Notes For Permit 16090832
Permit Number 16090832
Review Stop B
Sequence Number 1
Notes
Date Text
2016-10-18 13:24:58****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. LS100, EGRESS WIDTH TABULATIONS, HAS A TYPO (BOTH
 FIRST AND SECOND FLOOR), 15SF PER PERSON FOR STORAGE,
 FBC TABLE 1004.1.2.
  
 2. LS100, REVISE TO SHOW COMPLIANCE WITH FBC TABLE 503,
 FBC 506. COMPLIANCE FOR THE ENTIRE BUILDING, ALL
 OCCUPANCIES, SHOULD BE SHOWN. INCREASES PER FBC 506 ARE
 TO BE SHOWN.
  
 FOR EXAMPLE, A101 SHOWS BUILDING AREA AS 82,003, LS100
 SHOWS BUILDING AREA AS 71,055. LS100 PROJECT SUMMARY
 DOES NOT INCLUDE S1 OCCUPANCY.
  
 3. LS201, MEDIUM CONFERENCE ROOM IS SHOWN AS 4,641 SF
 ON THIS PAGE, APPEARS THAT THIS IS NOT CORRECT. REVISE
 OR CLARIFY, FBC 107.
  
 4. LS201, MEDIUM CONFERENCE ROOM OCCUPANT LOAD WAS
 CALCULATED AT 100 SF PER PERSON. CONFERENCE ROOMS ARE
 TYPICALLY ASSEMBLY WITH 15 SF PER PERSON.
  
 EITHER REVISE OR SEND A LETTER VIA EMAIL WHICH EXPLAINS
 RATIONALE. SEE PREVIOUS COMMENT. IF THIS ROOM IS
 INTENDED TO BE 4,641 SF, THE OCCUPANT LOAD SHOULD BE
 310 AND REQUIRES ANOTHER EXIT. IF THIS ROOM IS 384 SF,
 AN OCCUPANT LOAD OF 4 (100 SF PER PERSON) IS NOT
 CORRECT AS TEN CHAIRS ARE SHOWN.
  
 5. LS201, 202, APPLICABLE TO ALL CONFERENCE ROOMS AND
 BREAK ROOMS, ALSO POSSIBLY ROOMS 103 AND 104 MEDIA
 ROOMS, THESE AREAS ARE TYPICALLY TREATED AS ASSEMBLY
 OCCUPANCY, 15 SF PER PERSON. REVISE PLAN OR CONTACT ME
 TO DISCUSS, FBC TABLE 1004.1.2. 100 SF PER PERSON DOES
 NOT APPEAR TO BE AN ADEQUATE DESIGN OCCUPANT LOAD FOR
 THESE SPACES.
  
 5. LS201, FITNESS ROOM OCCUPANT LOAD WAS CALCULATED AT
 100 SF PER PERSON. SEE FBC TABLE 1004.1.2, 50 SF PER
 PERSON REQUIRED.
  
 6. CLARIFY WHICH ROOMS WERE CONSIDERED ASSEMBLY
 OCCUPANCY WHEN CALCULATING THE TOTAL SF AREA AND
 OCCUPANT LOAD IN EGRESS WIDTH TABULATIONS ON LS100,
 FBC107, FS553.
  
 7. LS201, ROOM 192, FBC 1008.1.10, REVISE PLAN TO
 CLARIFY ELECTRIC ROOM FUNCTION. IF PANIC BARS ARE NOT
 REQUIRED, REVISE PLAN TO INDICATE THAT THIS ROOM DOES
 NOT CONTAIN EQUIPMENT AS DESCRIBED IN THIS SECTION. IF
 PANIC BARS ARE REQUIRED DUE TO EQUIPMENT, REVISE PLAN
 TO NOTE AND REVISE TO OUTSWING DOORS.
  
 8. LS201, ROOM 105 IS ASSEMBLY OCCUPANCY WITH AN
 OCCUPANT LOAD OVER 49. EXIT STRATEGY IS NOT CLEAR. THE
 SE AND SW DOORS APPEAR TO LEAD TO THE SAME EXIT DOOR
 AND NEITHER HAS EXIT LIGHTS. THE DOOR AT THE REAR LEADS
 TO A GREEN ROOM, PURPOSE UNKNOWN WITH NO OCCUPANT LOAD
 SHOWN, WITH AN INSWING DOOR.
  
 REVISE PLAN TO CLARIFY EXIT STRATEGY, INCLUDE EXIT
 LIGHTS AS NEEDED, NUMBER OF OCCUPANTS FOR EACH SPACE.
  
 NOTE THAT PER FBC 1008.1.10 ALL DOORS IN THE MEANS OF
 EGRESS FOR ASSEMBLY TO HAVE PANIC DEVICES, FBC 1004.6.
 THE DOOR SCHEDULE WAS NOT REVIEWED AT THIS TIME AS
 EGRESS PATH IS NOT CLEAR.
  
 9. LS201, NO INFORMATION WAS PROVIDED REGARDING THE
 EXISTING COMMAND CENTER AND HOW EXITING WILL BE
 AFFECTED BY THE PROPOSED NEW COMMAND CENTER. PROVIDE
 INFORMATION REGARDING THE DOORS WHICH PREVIOUSLY LED
 DIRECTLY TO THE OUTDOORS WHICH WILL NOW LEAD TO THE NEW
 COMMAND CENTER. IF THESE DOORS ARE EXIT DOORS, HOW WILL
 TRAVEL DISTANCE BE AFFECTED? WHAT OCCUPANCY
 CLASSIFICATIONS DO THESE DOORS SERVE?
  
 10. LS201, EXITING FOR THE UPS ROOM IS NOT CLEAR. ONE
 DOOR LEADS TO THE EXISTING COMMAND CENTER, THE OTHER
 DOOR LEADS THROUGH THE ELECTRICAL ROOM. FBC 1014.2,
 REVISE PLAN TO SHOW COMPLIANCE.
  
 11. LS202, THE WEST CONFERENCE ROOM IS NOT LABELED AND
 LACKS AN OCCUPANT LOAD, FBC 107, SEE ALSO OTHER
 COMMENTS REGARDING OCCUPANT LOAD. REVISE PLAN TO
 INCLUDE ALL OCCUPANT LOAD FOR ALL SPACES.
  
 12. OCCUPANT LOAD TOTALS DO NOT APPEAR CORRECT. FOR
 INSTANCE, LS202 SHOWS OCCUPANT LOAD FOR THE BUSINESS
 AREA WHICH IS DIVIDED INTO ROOMS CALCULATED ON THE
 TOTAL RATHER THAN BY ROOM. FBC 107 AND FBC CHAPTER 10,
 AN ACCURATE OCCUPANT LOAD IS REQUIRED FOR C.O., TO
 CONFIRM COMPLIANCE WITH LIFE SAFETY REQUIREMENTS, AND
 FOR THRESHOLD BUILDING DETERMINATION. REVISE PLAN.
  
 13. FBC 1014.2, CLARIFY THE NUMBER OF OCCUPANTS
 CALCULATED TO TRAVEL THROUGH THE BREAK ROOM TO REACH
 THE REQUIRED EXIT. HOW WILL THE EGRESS PATH BE KEPT
 CLEAR OF TABLES AND CHAIRS? ASSEMBLY IS CONSIDERED A
 HIGHER RISK THAN BUSINESS. REVISE PLAN TO CLARIFY HOW
 COMPLIANCE WITH THE REQUIREMENT THAT A DISCERNIBLE PATH
 OF EGRESS TRAVEL TO AN EXIT WILL BE MET. FEEL FREE TO
 CONTACT ME TO DISCUSS.
  
 14. REVISE PLAN TO CLARIFY PURPOSE OF THE STAGE SHOWN
 ON THE FIRST FLOOR. VERTICAL ACCESSIBILITY MAY APPLY,
 FBC 5TH EDITION ACCESSIBILITY 201.1.1, 203.9. IF
 EXCEPTIONS ARE APPLICABLE, REVISE PLAN TO INCLUDE
 EXCEPTION(S).
  
 15. A321, A322, A323, TEXT IS NOT LEGIBLE IN SEVERAL
 LOCATIONS; CHECK ALL AND PROVIDE LEGIBLE TEXT.
  
 16. A760, THE GRAB BAR IS TO BE INSTALLED 33 TO 36
 INCHES MEASURED TO THE TOP OF THE BAR, FBC 5TH EDITION
 ACCESSIBILITY 609.4. THE DETAILS DO NOT COMPLY AS THE
 BAR IS SHOWN TOO HIGH, REVISE ALL AFFECTED DETAILS.
  
 17. A800 SHOWS CARD READERS ON SOME DOORS. A SEPARATE
 PERMIT IS REQUIRED FOR ACCESS CONTROL. THIS ITEM IS NOT
 BEING REVIEWED AT THIS TIME.
  
 18. S001, TABLE 1607.1, REVISE TO INCLUDE ASSEMBLY AREA
 LIVE LOAD.
  
 19. THREE SETS OF PLANS REQUIRED; SEE THRESHOLD REVIEW.
  
 20. A CONSTRUCTION TRAILER IS SHOWN ON SHEET M104. THIS
 REQUIRES A SEPARATE PERMIT AND HAS NOT BEEN REVIEWED AT
 THIS TIME.
  
 21. SEE IMPACT FEE REVIEW. THIS IS TO BE PAID PRIOR TO
 PERMIT ISSUANCE.
  
  