 2201 45TH STREET
 HOSPITAL ELECTRIC UPGRADE
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 TEMPORARY FEEDERS ARE UNDERSIZED BASED ON THE PROPOSED
 SIZE OF CONDUCTORS WITH OVERCURRENT PROTECTION.
 ADDITIONAL INFORMATION IS NEEDED REGARDING CONDUCTOR
 PROPERTIES, PHYSICAL PROTECTION, BUNDLING, ETC. NEC
 310.10
  
 VERIFY THAT ALL REQUIRED EGRESS DOORS FROM THE
 ELECTRICAL EQUIPMENT ROOMS SWING IN THE APPROPRIATE
 DIRECTION AND ARE THE PROPER HEIGHT AND WIDTH. NEC
 110.26
  
 THE FOLLOWING ITEMS REQUIRE SOME CLARIFICATION:
  
 HAVE THEN NOTED EXISTING PANELS BEEN INCLUDED OR
 ABANDONED WITH THE NEW PLANS? PANELS ECB, ELS, PNA,
 PNB, RMI, H1ECRDP, H1ELSA, CHLRRAD.
  
 VERIFY OR INDICATE THE CORRECT VOLTAGE FOR PANEL NPB
 AND TRANSFORMER T-PB WHICH IS FED FROM SECTION 3 OF THE
 NEW MSB.
  
 PANEL RZA1 IS LISTED TWICE AND SHOWN AT 80 AND AT
 90AMPS. IT IS SHOWN AS FED FROM BOTH CRPD2 AND LSDP2.
  
 HAS THE EXISTING ATS 4 BEEN INCLUDED OR ABANDONDED?
  
  