Plan Review Notes
Plan Review Notes For Permit 16090809
Permit Number 16090809
Review Stop Z
Sequence Number 2
Notes
Date Text
2017-03-07 14:59:32FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSES TO COMMENTS.
  
 1) REPEAT COMMENT: THE DEMOLITION OF THE EXISTING
 GENERATOR AND THE CONSTRUCTION OF A NEW GENERATOR PAD
 AND LOCATING A 1,000 KW GENERATOR ON THE PAD REQUIRES
 AN AMENDMENT TO THE WEST PALM HOSPITAL COMMUNITY
 SERVICE PLANNED DEVELOPMENT SITE PLAN. A MINOR PLANNED
 DEVELOPMENT APPLICATION SHALL BE FILED WITH THE
 PLANNING DIVISION AND RECEIVE APPROVAL, PRIOR TO THE
 ZONING APPROVAL OF THIS PERMIT.
  
 2) WHILE THE GENERATOR ITSELF IS ENCLOSED IN A HOUSING,
 THE FUELING ASSEMBLY IS EXPOSED ON THE END OF THE
 GENERATOR, WHICH REQUIRES THAT THERE BE A SCREEN WALL
 WITH HEDGES CONSTRUCTED ON THE NORTH AND WEST SIDES OF
 THE GENERATOR (THE EAST AND SOUTH ARE SCREENED BY THE
 EXISTING BUILDING WALLS). A PERMIT FOR THE SCREEN WALL
 AND HEDGES SHALL BE SUBMITTED, APPROVED AND CONSTRUCTED
 PRIOR TO THE FINAL PERMIT INSPECTION FOR THE GENERATOR.
 THE SCREENING NEEDS TO BE INCLUDED ON THE MINOR PLANNED
 DEVELOPMENT AMENDMENT.
  