2017-02-23 09:04:351ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16090809
 2/23/17
  
 1) DWG NO 500: IDENTIFY THE DAY TANK ON THE DRAWINGS
 AND SHOW THE VENT PIPING RUNS AND DISCHARGE LOCATIONS-
 SEE SECTION 1305.7 . PLEASE PROVIDE THE TYPES AND SIZES
 OF VENT PIPES.
  
 2) DWG NO 500: PROVIDE THE CLEARANCE DISTANCE
 MEASUREMENTS FOR THE GENERATOR COMBUSTION AND RADIATOR
 EXHAUST OUTLETS TO GRADE- SEE SECTION 501.3.1
  
 3) CLARIFY THE SCOPE OF WORK PERTAINING TO THE LARGE
 INDOOR GENERATOR FUEL TANKS. IT APPEARS FROM THE
 DRAWINGS THAT EITHER ONE OR TWO NEW TANKS ARE BEING
 INSTALLED IN THE EQUIPMENT ROOM ADJACENT TO THE
 GENERATOR ROOM. PROVIDE SPECIFICATIONS ON THE PLAN AND
 SUBMIT PRODUCT DATA SHEETS FOR THE TANKS. REVIEW
 CHAPTER 9 NFPA 30 AND SHOW COMPLIANCE WITH ALL
 APPLICABLE SECTIONS FOR INDOOR STORAGE OF FLAMMABLE AND
 COMBUSTIBLE LIQUIDS.
  
 4) THE SUBMITTED NOA'S FOR THE AIR INTAKE AND THE
 EXHAUST LOUVERS DO NOT INCLUDE THE INSTALLATION
 DRAWINGS- PLEASE PROVIDE COMPLETE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  