Notes
Date Text
2017-02-27 12:35:46THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) REGARDING THE NEW DAY TANK, THERE IS INSUFFICIENT
 DETAIL INDICATED TO DETERMINE OR ENSURE COMPLIANCE OF
 THE DAY TANK WITH NFPA 30 AND OTHER APPLICABLE CODES.
  
 PLEASE COMPLETE A REVIEW AND PROVIDE AN DETAILED
 NOTE/NARRATIVE.
  
  
  
  
 2) REGARDING THE MAIN GENERATOR, THERE IS INSUFFICIENT
 DETAIL INDICATED TO DETERMINE OR ENSURE COMPLIANCE OF
 ANY PROPOSED ACESSORY FULE TANK WITH NFPA 30 AND OTHER
 APPLICABLE CODES.
  
 PLEASE COMPLETE A REVIEW AND PROVIDE AN DETAILED
 NOTE/NARRATIVE.
  
  
  
  
 3) REGARDING THE MAIN GENERATOR LOCATION AND EXISTING
 VAULT, THERE IS INSUFFICIENT DETAIL INDICATED TO
 DETERMINE OR ENSURE COMPLIANCE WITH NFPA 110 AND OTHER
 APPLICBALE CODES.
  
 IF THIS IS AN FP&L VAULT, DOES/WILL FP&L ALLOW THE
 GENERATOR THIS CLOSE ? PLEASE PROVIDE AND APPLICABLE
 REVIEW AND DETAILED NOTE/NARRATIVE.
  
 DOES THIS INSTALLATION MEET THE REQUIREMENTS OF NFPA
 110? PLEASE PROVIDE APPLICABLE DETAIL, INCLUDING
 DIMENSIONS.
  
 DOES THE MANUFACTURES SPEC'S PROVIDE A MINIMUM
 DIMENSION TO THE NEAREST STRUCTURE?
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  