| 2017-02-27 12:35:46 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) REGARDING THE NEW DAY TANK, THERE IS INSUFFICIENT |
| | DETAIL INDICATED TO DETERMINE OR ENSURE COMPLIANCE OF |
| | THE DAY TANK WITH NFPA 30 AND OTHER APPLICABLE CODES. |
| | |
| | PLEASE COMPLETE A REVIEW AND PROVIDE AN DETAILED |
| | NOTE/NARRATIVE. |
| | |
| | |
| | |
| | |
| | 2) REGARDING THE MAIN GENERATOR, THERE IS INSUFFICIENT |
| | DETAIL INDICATED TO DETERMINE OR ENSURE COMPLIANCE OF |
| | ANY PROPOSED ACESSORY FULE TANK WITH NFPA 30 AND OTHER |
| | APPLICABLE CODES. |
| | |
| | PLEASE COMPLETE A REVIEW AND PROVIDE AN DETAILED |
| | NOTE/NARRATIVE. |
| | |
| | |
| | |
| | |
| | 3) REGARDING THE MAIN GENERATOR LOCATION AND EXISTING |
| | VAULT, THERE IS INSUFFICIENT DETAIL INDICATED TO |
| | DETERMINE OR ENSURE COMPLIANCE WITH NFPA 110 AND OTHER |
| | APPLICBALE CODES. |
| | |
| | IF THIS IS AN FP&L VAULT, DOES/WILL FP&L ALLOW THE |
| | GENERATOR THIS CLOSE ? PLEASE PROVIDE AND APPLICABLE |
| | REVIEW AND DETAILED NOTE/NARRATIVE. |
| | |
| | DOES THIS INSTALLATION MEET THE REQUIREMENTS OF NFPA |
| | 110? PLEASE PROVIDE APPLICABLE DETAIL, INCLUDING |
| | DIMENSIONS. |
| | |
| | DOES THE MANUFACTURES SPEC'S PROVIDE A MINIMUM |
| | DIMENSION TO THE NEAREST STRUCTURE? |
| | |
| | |
| | |
| | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |