| 2016-10-13 14:46:39 | 1ST REVIEW FBC-2014 MECHANICAL |
| | PERMIT #16090809 |
| | 10/13/16 |
| | |
| | 1) DWG NO. D500: PROVIDE AC COOLING AND HEATING |
| | CALCULATIONS FOR THE NEW MINI-SPLIT SYSTEMS. |
| | |
| | 2) D500: CLARIFY THE SCOPE OF WORK FOR THE GENERATOR- |
| | NEW OR RELOCATED? A) PROVIDE AN EQUIPMENT SCHEDULE THAT |
| | INDICATES THE MAKE AND MODEL OF THE GNERATOR, |
| | ELECTRICAL DATA, FUEL TYPE, ETC. B) PROVIDE AN ENLARGED |
| | DIMENSIONED DRAWING AND SCHEMATIC, WITH DETAILS AND |
| | NOTES IDENTIFYING THE TYPE AND SIZE OF EXHAUST VENTING, |
| | AND FUEL PIPING. CLARIFY HOW FUEL IS BEING STORED AND |
| | SUPPLIED TO THE GENERATOR AND WHAT THE TYPE OF FUEL IS- |
| | DIESEL, GAS, BOTH? C) REFER TO SECTION 501.3.1 AND SHOW |
| | ALL REQUIRED CLEARANCE DISTANCE MEASUREMENTS FOR THE |
| | SIDEWALL RADIATOR AND GENERATOR EXHAUST OUTLETS. D) |
| | SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE GENERATOR |
| | WITH SHOP DRAWING APPROVAL SIGNATURE BY THE ENGINEER OF |
| | RECORD. |
| | |
| | 3) D500: THE WIND LOAD CALCULATIONS AND FASTENING NOTES |
| | FOR A ROOFTOP AC STAND DO NOT CORRELATE WITH THE |
| | PROPOSED GROUND MOUNTED CONDENSER INSTALLATIONS- PLEASE |
| | PROVIDE CORRECT THE CALCULATIONS AND NOTES. |
| | |
| | 4) SUBMIT FL. PRODUCT APPROVALS AND/OR MIAMI-DADE NOA'S |
| | FOR THE GREENHECK AIR INTAKE LOUVER, AND THE RUSKIN |
| | EXHAUST LOUVER. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 561-805-6719 |
| | [email protected] |
| | |