Plan Review Notes
Plan Review Notes For Permit 16090809
Permit Number 16090809
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2016-10-18 14:56:43THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET D100 - THERE IS AN INCORRECT YEAR REFERENCE TO
 THE FFPC 5TH EDITION, IT SHOULD INDICATE 2012.
  
 PLEASE CORRECT AND ENSURE COMPLIANCE.
  
  
  
 2) SHEET D101 - THERE IS NO INDICATIONS AND IT IS
 UNCLEAR HOW THE LIFE SAFETY FIRE ALARM SYSTEM WILL BE
 MAINTAINED THROUGHOUT THE CONSTRUCTION PERIOD.
  
 PLEASE PROVIDE A NOTE OR SHORT NARRATIVE IF AND HOW THE
 FIRE ALARM WILL BE MAINTAINED THROUGHOUT THE HOSPITAL.
  
 PER NFPA 101, CHAPTER 9 A FIRE WATCH SHALL BE
 MAINTAINED ANY TIME A SYSTEM IS DOWN FOR MORE THAN 4
 HOURS.
  
 9.6.1.6* WHERE A REQUIRED FIRE ALARM SYSTEM IS OUT OF
 SERVICE FOR MORE THAN 4 HOURS IN A 24-HOUR PERIOD, THE
 AUTHORITY HAVING JURISDICTION SHALL BE NOTIFIED, AND
 THE BUILDING SHALL BE EVACUATED, OR AN APPROVED FIRE
 WATCH SHALL BE PROVIDED FOR ALL
 PARTIES LEFT UNPROTECTED BY THE SHUTDOWN UNTIL THE FIRE
 ALARM SYSTEM HAS BEEN RETURNED TO SERVICE.
  
  
  
 3) SHEET D 301 - THERE IS AN INDICATION OF A NEW
 GENERATOR. ANY NEW GENERATOR INSTALLATION IS NOT
 APPROVED UNDER THIS PERMIT.
  
 PLEASE PROVIDE A NOTE INDICATING THAT THE NEW GENERATOR
 SHALL BE UNDER SEPARATE PERMIT.
  
  
  
 4) SHEET D304 - THERE IS FIRE ALARM WORK INDICATED IN
 THE NOTES SECTION. ANY FIRE ALARM WORK SHALL BE
 COMPLETED BY QUALIFIED LIOFE SAFETY CONTRACTORS UNDER
 SEPARATE SHOP DRAWINGS.
  
 PLEASE PROVIDE A NOTE INDICATING AND ACKNOWLEDGING THE
 ABOVE.
  
  
  
 5) SHEET D 306 - THERE IS FIRE SPRINKLER WORK
 INDICATED. ANY FIRE SPRINKLER WORK SHALL BE COMPLETED
 BY QUALIFIED LIFE SAFETY CONTRACTORS UNDER SEPARATE
 SHOP DRAWINGS.
  
 PLEASE PROVIDE A NOTE INDICATING AND ACKNOWLEDGING THE
 ABOVE.
  
  
  
 6) SHEET 307 - THERE IS AN INDICATION OF A NEW
 GENERATOR. ANY NEW GENERATOR INSTALLATION IS NOT
 APPROVED UNDER THIS PERMIT.
  
 PLEASE PROVIDE A NOTE INDICATING THAT THE NEW GENERATOR
 SHALL BE UNDER SEPARATE PERMIT.
  
  
  
 7) SHEET 310, D322 AND OTHER APPLICABLE GENERATOR
 EXHAUST SHEETS - THE NEW GENERATOR(S) EXHAUST APPEARS
 TO IN AN AREA OF MULTIPLE WINDOWS AND INHABITABLE
 AREAS.
  
 PLEASE PROVIDE A DETAILED REVIEW INDICATING COMPLIANCE
 WITH NFPA 110. CHAPTER 7
  
 7.10 EXHAUST SYSTEM.
 7.10.1 THE EXHAUST SYSTEM EQUIPMENT AND INSTALLATION,
 INCLUDING PIPING, MUFFLER, AND RELATED ACCESSORIES,
 SHALL BE IN ACCORDANCE WITH NFPA37, STANDARD FOR THE
 INSTALLATION AND USE OF STATIONARY COMBUSTION ENGINES
 AND GAS TURBINES, AND OTHER APPLICABLE STANDARDS.
  
 7.10.2 EXHAUST SYSTEM INSTALLATION SHALL BE GASTIGHT TO
 PREVENT EXHAUST GAS FUMES FROM ENTERING INHABITED ROOMS
 OR BUILDINGS AND TERMINATE IN SUCH A MANNER THAT TOXIC
 FUMES CANNOT REENTER A BUILDING OR STRUCTURE,
 PARTICULARLY THROUGH WINDOWS,
 AIR VENTILATION INLETS, OR THE ENGINE AIR-INTAKE
 SYSTEM.
  
  
  
 8) PLEASE PROVIDE PLAN SHEET REVISION CLOUDS OR
 NUMBERED NARRATIVE RESPONSES TO THE ABOVE.
  
  
  
  
 9) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  