| 2016-10-13 11:37:27 | JOB PERMIT NUMBER: 16090809 |
| | JOB ADDRESS: 2201 45TH ST |
| | WEST PALM BEACH FLORIDA |
| | DATE: OCTOBER 13, 2016 |
| | ELECTRICAL PLAN REVIEW COMMENTS |
| | |
| | THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH NEC |
| | 2011, (NATIONAL ELECTRICAL CODE) AND FBC 2014, (FLORIDA |
| | BUILDING CODE) AS WELL AS THE CITY OF WEST PALM BEACH |
| | AMENDMENTS. BELOW IS A LIST OF ITEMS THAT HAVE BEEN |
| | NOTED. |
| | |
| | 1] PROVIDE A FIRE PENETRATION DETAIL FOR FIRE WALLS, |
| | SMOKE BARRIERS, AND FIRE PARTITIONS. SHOW THROUGH |
| | PENETRATION DETAILS FOR ALL NEWLY INSTALLED RUNS. |
| | FBC-714 |
| | |
| | 2] IDENTIFY FIRE & SMOKE RATING OF ANY WALLS TO BE |
| | PENETRATED OR HAVE PENETRATIONS REMOVED WITHIN THE WORK |
| | AREAS. FBC-704 |
| | |
| | 3] PROVIDE FPL LINE TO LINE AVAILABLE FAULT CURRENT TO |
| | VERIFY AIC RATINGS AND SHORT-CIRCUIT CALCULATIONS OF |
| | THE PROPOSED ELECTRICAL SYSTEM. NEC 110.9, 110.10, & |
| | 110.24 |
| | |
| | 4] PROVIDE DOCUMENTATION OF SELECTIVE COORDINATION TIME |
| | CURRENT CHARACTERISTICS CHARTS OF THE SERIES |
| | COMBINATION. ENSURE GFP EQUIPMENT SHALL BE COORDINATED |
| | IN A MATTER THAT THE LOAD SIDE SHALL REMAIN PASSIVE |
| | DURING INTERRUPTION OF THE LINE SIDE CURRENT LIMITING |
| | DEVICE. NEC 240.86, 517.17 |
| | |
| | 5] SHOW GFP PROTECTION OF EQUIPMENT ON THE ONE-LINE |
| | DIAGRAMS FOR EACH DISCONNECT RATED 1000 AMPERES OR MORE |
| | ON WYE SYSTEMS OF MORE THAN 150 VOLTS TO GROUND. NEC |
| | 215.9,230.95, & 240.13 |
| | |
| | 6] ADD NOTES FOR DEDICATED EQUIPMENT SPACE EXTENDING |
| | FROM THE FLOOR TO 6' ABOVE THE EQUIPMENT OR STRUCTURE |
| | CEILINGS. NO FOREIGN SYSTEM PIPING ALLOWED IN THIS |
| | ZONE. NEC 110.26(E)(1) |
| | |
| | 7] ADD NOTES FOR ELECT ROOMS WITH EQUIPMENT RATED OVER |
| | 1200 AMPERES ENTRANCE & EGRESS DOORS SHALL BE MINIMUM |
| | 24'' WIDE 6'6'' HIGH WITH PANIC HARDWARE DEVICES. |
| | DEMOLITIONS OF WALLS IN ORDER TO INSTALL EQUIPMENT WILL |
| | REQUIRE A BUILDING PERMIT. NEC 110.26(C)(2)(3 |
| | |
| | 8] NEC 110.16 ARC-FLASH HAZARD WARNING: ELECTRICAL |
| | EQUIPMENT IN OTHER THAN DWELLING UNITS LIKELY TO |
| | REQUIRE SERVICED WHILE ENERGIZED SHALL BE FIELD MARKED |
| | TO WARN AGAINST POTENTIAL ARC-FAULT HAZARDS. |
| | |
| | 9] SHOW COMPLIANCE WITH NEC 110.22 A NOTE WILL |
| | SUFFICE.TESTED OR ENGINEERED SERIES COMBINATION SYSTEMS |
| | SHALL BE LEGIBLY MARKED IN THE FIELD TO INDICATE THE |
| | EQUIPMENT HAS BEEN APPLIED WITH SERIES COMBO RATING. |
| | THE IDENTIFICATION SHOULD BE READILY ACCESSIBLE AND |
| | SUITABLE FOR THE ENVIRONMENT INVOLVED. |
| | |
| | 10] SINCE MULTIPLE SERVICES ARE INVOLVED FOR SPECIAL |
| | CONDITIONS AND CAPACITY REQUIREMENTS APPLY A PERMANENT |
| | PLAQUE WITH A DIRECTORY DENOTING ALL OTHER SERVICE |
| | DISCONNECTS SUPPLYING THE BUILDING. NEC 230.2(E) |
| | |
| | 11] CLARIFY WHY GENERATOR ROOM DOESN'T HAVE A FIRE |
| | SUPPRESSION SYSTEM PER NEC 700.12 (GENERAL |
| | REQUIREMENTS) |
| | |
| | 12] FEEDER 400N CANNOT EXCEED 2 % VOLTAGE DROP IN |
| | ACCORDANCE WITH FBC-E SEC C405.7.3 |
| | |
| | 13] NEW T-GEN HAS WRONG SIZE PRIMARY CONDUCTORS FOR THE |
| | TRANSFORMER, # 8 AWG CONDUCTOR IS ONLY GOOD FOR 50 AMP |
| | PLEASE CORRECT ACCORDINGLY. |
| | |
| | 14] TAPS FROM COPPER TO ALUMINUM SHALL USE PROPERLY |
| | IDENTIFIED SPLICING CONNECTION RATED FOR DISSIMILAR |
| | METALS. ALL TERMINAL LUGS SHALL BE TIGHTENED TO LISTED |
| | TORQUE AND MARKED VISIBLY TO THE FIELD INSPECTOR. NEC |
| | 110.14 |
| | |
| | 15] SHOW TEMPORARY GUTTER SIZE TO COMPLY WITH NEC |
| | 366,376,378 AND ALL TEMP CABLE WITH FINE STRANDED |
| | CONDUCTORS SHALL BE TERMINATED PROPERLY AND APPROVED BY |
| | INSPECTOR PER NEC 110.14 |
| | |
| | 16] PRIOR TO THE COMMENCEMENT OF ANY WORK ITS HIGHLY |
| | RECOMMENDED TO CONTRACTOR TO REQUEST A MEETING WITH ALL |
| | PARTIES INVOLVED AND THE BUILDING DEPARTMENT TO DISCUSS |
| | CONSTRUCTION PHASING. |
| | |
| | 17] FIRE PUMPS SHALL BE SUBMITTED UNDER A SEPARATE |
| | PERMIT IF BEING WORKED ON. |
| | |
| | PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| | MENTIONED ITEMS.WHEN RESUBMITTING, FOR A QUICKER RETURN |
| | ON YOUR RE-SUBMITTAL, PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. |
| | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. IF |
| | YOU HAVE FURTHER QUESTIONS, PLEASE DON'T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | FBC 2014 5TH ED. NEC 2011 |
| | MARIO VALDES |
| | ELECTRICAL PLAN EXAMINER |
| | 561-805-6713 |
| | [email protected] |
| | |