2016-09-23 15:28:50PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 REVISION DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 2) THE 2ND FLOOR EQUIPMENT IS BEING INCREASED FROM TWO
 AND A HALF TONS TO THREE TONS. THIS IS NOT AN EXACT
 CHANGEOUT. SUBMIT EQUIPMENT SIZING CALCULATIONS AS
 REQUIRED BY FBCR M1401.3
  
 3) LABEL THE DRAWINGS TO SHOW WHICH FLOOR THEY ARE FOR.
 FBC 107.2.1
  
 4) SPECIFY THE SIZE OF ALL NEW DUCT WORK ON THE PLANS.
 THE DUCTS FOR THE TWO DROPS IN THE LIVING ROOM AND ONE
 OF THE DROPS IN THE KITCHEN ARE NOT SIZED ON THE PLANS.
 FBC 107.2.1
  
  