| Plan Review Notes For Permit 16090750 |
| Permit Number |
16090750 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-09-23 15:28:50 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | REVISION DENIED BY MECHANICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. | | | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | | THE PERSON RESPONSIBLE FOR THE DESIGN. | | | | | | 2) THE 2ND FLOOR EQUIPMENT IS BEING INCREASED FROM TWO | | | AND A HALF TONS TO THREE TONS. THIS IS NOT AN EXACT | | | CHANGEOUT. SUBMIT EQUIPMENT SIZING CALCULATIONS AS | | | REQUIRED BY FBCR M1401.3 | | | | | | 3) LABEL THE DRAWINGS TO SHOW WHICH FLOOR THEY ARE FOR. | | | FBC 107.2.1 | | | | | | 4) SPECIFY THE SIZE OF ALL NEW DUCT WORK ON THE PLANS. | | | THE DUCTS FOR THE TWO DROPS IN THE LIVING ROOM AND ONE | | | OF THE DROPS IN THE KITCHEN ARE NOT SIZED ON THE PLANS. | | | FBC 107.2.1 | | | | | | |
|