| Plan Review Notes For Permit 16090688 |
| Permit Number |
16090688 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-10-26 16:28:39 | 2ND ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 | | | PENDING COMMENTS: | | | | | | | | | 3. PER FBC EC-405.7- SHOW COMPLIANCE OF 50% OF THE | | | RECEPTACLES 120V, 15 & 20AMP TO BE AUTOMATICALLY | | | CONTROLLED (PER YOUR NARRATIVE PLEASE NOTE THAT YOU CAN | | | PROVIDED VALUATION OF PROPERTY IN ORDER TO DETERMINE IF | | | PROJECT IS EXEMPT FROM THE REQUIREMENTS OF THE FBC EC.) | | | VALUATION IS BASED ON THE TENANT SPACE UNDER | | | CONSTRUCTION. | | | 6. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE | | | TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING | | | THIS PROJECT. | | | | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | |
|