Plan Review Notes
Plan Review Notes For Permit 16090688
Permit Number 16090688
Review Stop E
Sequence Number 2
Notes
Date Text
2016-10-26 16:28:392ND ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 PENDING COMMENTS:
  
  
 3. PER FBC EC-405.7- SHOW COMPLIANCE OF 50% OF THE
 RECEPTACLES 120V, 15 & 20AMP TO BE AUTOMATICALLY
 CONTROLLED (PER YOUR NARRATIVE PLEASE NOTE THAT YOU CAN
 PROVIDED VALUATION OF PROPERTY IN ORDER TO DETERMINE IF
 PROJECT IS EXEMPT FROM THE REQUIREMENTS OF THE FBC EC.)
 VALUATION IS BASED ON THE TENANT SPACE UNDER
 CONSTRUCTION.
 6. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING
 THIS PROJECT.
  
  