Plan Review Notes
Plan Review Notes For Permit 16090688
Permit Number 16090688
Review Stop B
Sequence Number 2
Notes
Date Text
2016-10-28 17:41:33****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. A4.3, DETAIL 2, GRAB BAR TO BE MEASURED TO THE TOP
 OF THE BAR, FBC 5TH EDITION ACCESSIBILITY 609.4.
  
 COMMENT NOT ADDRESSED, SAME SHEET SUBMITTED. RESPONSE
 LETTER STATES THAT THE DETAIL WAS REVISED, BUT NO
 REVISION WERE MADE TO THIS SHEET.
  
 2. A4.3, PLANS REFER TO OUTDATED CODE SECTIONS (FOR
 INSTANCE, 11.4.22.2). UPDATE ALL REFERENCES. PLAN
 REFERS TO ADAAG; FLORIDA BUILDING CODE IS APPLICABLE.
  
 COMMENT NOT ADDRESSED, SAME SHEET SUBMITTED. RESPONSE
 LETTER STATES SHEET A4.3 WAS REMOVED FROM PERMIT
 APPLICATION. THE SAME SHEET IS IN THE PLAN.
  
 3. A4.3, SEE FBC 5TH EDITION ACCESSIBILITY 604.4, SEAT
 HEIGHT OF WATER CLOSET IS TO BE 17 IN MINIMUM AND 19
 INCHES MAXIMUM. DETAIL 2 SHOWS THE MEASUREMENT TO THE
 TOP OF THE LID. REVISE AND CHECK ALL
 GRAPHICS/DIMENSIONS.
  
 COMMENT NOT ADDRESSED, SAME SHEET SUBMITTED. RESPONSE
 LETTER STATES SHEET A4.3 WAS REMOVED FROM PERMIT
 APPLICATION. THE SAME SHEET IS IN THE PLAN.
  
 4. FUNCTION OF THE LIVE KITCHEN IS NOT CLEAR. THE FLOOR
 PLAN DOES NOT SHOW SEATS WHICH ARE SHOWN ON A5.3.
 ACCESSIBILE SEATING IS NOT SHOWN. PROVIDE MORE
 INFORMATION FBC 107.
  
 RESPONSE LETTER STATES THIS IS A FUNCTIONAL KITCHEN.
 ACCESSIBLE SEATING NOT SHOWN. FUNCTION OF SPACE IS
 STILL NOT ENTIRELY CLEAR (SALES DEMO, CLASSES, PARTY?),
 SO IT IS NOT POSSIBLE TO PROVIDE A CODE REFERENCE.
 HOWEVER, ACCESSIBLE SEATING IS REQUIRED.
  
 5. A1.0, "OFFICE GROUP M MERCANTILE WHAREHOUSE"
 (S.I.C.); REVISE TO WHAT APPEARS TO BE CORRECT
 CLASSIFICATION, MERCANTILE. OFFICE IS BUSINESS,
 WAREHOUSE IS S1 OR S2.
  
 2ND REVIEW, THIS HAS NOW BEEN CHANGED TO "MAJOR
 MERCANTILE." PLEASE EXPLAIN, THIS CLASSIFICATION IS NOT
 IN THE FLORIDA BUILDING CODE. REVISE, SEE FBC CHAPTER
 3.
  
 NEW COMMENTS:
  
 6. PLEASE HAVE ARCHITECT EXPLAIN INCONSISTENCY IN
 ARCHITECT'S SIGNATURE BETWEEN 9/16 AND 10/14, ORIGINAL
 SHEETS AND REVISED SHEETS A1.0 AND A4.2.
  
 WHEN RESUBMITTING, PLEASE SUBMIT A COMPLETE SET (A
 SHEETS) IN ADDITION TO THE SHEETS WHICH WILL BE REVISED
 AS A SET IS BEING RETAINED.
  
 7. SEE FLORIDA STATUTE 553.80(2)(B):
  
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS'
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
 NOTE THAT THE STATUTE STATES "SHALL IMPOSE," NOT "MAY
 IMPOSE."
  
 DUE TO THE MANNER IN WHICH THE COMMENTS WERE ADDRESSED,
 PLEASE HAVE ARCHITECT PROVIDE A RESPONSE LETTER (RATHER
 THAN THE "PROJECT MANAGER"). PLEASE HAVE ARCHITECT
 CONTACT ME IF HE OBJECTS TO THIS REQUEST.
  
 8. THE TITLE BLOCK IS TO INCLUDE THE ARCHITECT BUSINESS
 NUMBER, FS481, FAC61G1.
  
  
  
  
  