| Plan Review Notes For Permit 16090688 |
| Permit Number |
16090688 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-09-26 14:49:24 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 | | | COMMENTS: | | | | | | 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE | | | PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE | | | PERMITS AND DATA CUT SHEET SUBMITTALS FOR ALL LOW | | | VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE | | | ALARM, ACCESS CONTROLS, CCTV, PHONE AND DATA, ETC. A | | | NOTE WILL SUFFICE. | | | 2. DRINKING FOUNTAIN GFCI TO BE READILY ACCESSIBLE, | | | SHOW OVERCURRENT AT PANELBOARD TO BE GFCI. A NOTE WILL | | | SUFFICE. | | | 3. PER FBC EC-405.7- SHOW COMPLIANCE OF 50% OF THE | | | RECEPTACLES 120V, 15 & 20AMP TO BE AUTOMATICALLY | | | CONTROLLED. | | | 4. SHOW GFCI PROTECTION FOR ALL RECEPTACLES LOCATED AT | | | LIVE KITCHEN AREAS. NEC 210.8B | | | 5. ADDRESS FIRE COMMENTS RELATED TO ELECTRICAL. | | | 6. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE | | | TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING | | | THIS PROJECT. | | | | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | |
|