Plan Review Notes
Plan Review Notes For Permit 16090662
Permit Number 16090662
Review Stop B
Sequence Number 1
Notes
Date Text
2016-09-20 10:39:59RESIDENTIAL (R3) REVISION, BUILDING REVIEW COMMENTS.
 CODE: FBC 5TH EDITION.
  
 1- PRODUCT APPROVAL FL17347-R1 SUBMITTED DOESN'T MEET
 THE DESIGN PRESSURES CALCULATED BY THE ENGINEER OF
 RECORD. SEE APPROVED DRAWING S-2. NEED TO PROVIDE
 PRODUCT APPROVAL (2 COPIES) THAT MEETS THE CALCULATED
 DESIGN PRESSURES AS REQUIRED BY FAC 61H20-3.002(33).
  
 2- THE LICENSE OF THE ENGINEER (JOHN HOLT PE #15252)
 WHO REVIEWED THE PRODUCT APPROVAL SUBMITTED IS
 SUSPENDED. PRODUCT APPROVALS SUBMITTED WILL BE SENT TO
 THE BOARD OF ENGINEERS FOR THEIR REVIEW.
 PLANS WERE TAKEN OVER BY ANOTHER PROFESSIONAL ENGINEER.
 SEE REVISED DRAWING S-2. NEW ENGINEER NEEDS TO REVIEW
 AND APPROVE THE DOORS PRODUCT APPROVAL AS REQUIRED BY
 SEC. 107.3.4.1 CITY AMENDMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]