| 2016-11-23 14:03:03 | JOB PERMIT NUMBER: 16090649 |
| | JOB ADDRESS: 444 BUNKER RD |
| | WEST PALM BEACH FLORIDA (COMMERCIAL SOLAR SYSTEM) |
| | DATE: NOVEMBER 23, 2016 |
| | ELECTRICAL PLAN REVIEW COMMENTS |
| | |
| | THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH NEC |
| | 2011, (NATIONAL ELECTRICAL CODE) AND FBC 2014, (FLORIDA |
| | BUILDING CODE) AS WELL AS THE CITY OF WEST PALM BEACH |
| | AMENDMENTS. SEE BELOW A LIST OF ITEMS NOTED. |
| | |
| | 1] PLANS REQUIRE SIGNING & SEALING BY AN ELECTRICAL |
| | ENGINEER IN ACCORDANCE WITH FS 471 |
| | |
| | 2] PROVIDE FPL AVAILABLE FAULT CURRENT LETTER & SHOW |
| | AIC CALCULATIONS TO VERIFY SHORT CIRCUIT RATINGS OF |
| | ELECTRICAL EQUIPMENT. NEC 110.24, 110.10, 110.9 |
| | |
| | 3] SUBMITTAL DOCUMENTS SHALL BE SUBMITTED IN TWO OR |
| | MORE SETS WITH EACH PERMIT APPLICATION. FBC 107 |
| | |
| | 4] PLEASE COMPLY WITH GROUNDING & BONDING PROVISIONS |
| | PER NEC 250.24, 250.28, 250.30. VERIFY GROUNDED |
| | CONDUCTOR IS'T ATTACHED TO ENCLOSURES ON LOAD SIDE |
| | CONNECTIONS, VERIFY EQUIPMENT GROUNDING CONDUCTOR |
| | SYSTEM IS IN PLACE TO CREATE AN EFFECTIVE GROUND |
| | CURRENT PATH, LASTLY VERIFY SEPARATELY DERIVED SYSTEMS |
| | IS PROPERLY GROUNDED WITH AN ELECTRODE & BONDED AS TO |
| | PREVENT OBJECTIONABLE CURRENT. |
| | |
| | PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| | MENTIONED ITEMS. WHEN RESUBMITTING, FOR A QUICKER |
| | RETURN ON YOUR RE-SUBMITTAL, PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM. CLOUDING THE CHANGES |
| | WILL BE GREATLY APPRECIATED. IF YOU HAVE FURTHER |
| | QUESTIONS, PLEASE DON'T HESITATE TO CONTACT ME |
| | DIRECTLY. |
| | |
| | 1ST REVIEW FBC 2014 5TH ED. NEC 2011 |
| | MARIO VALDES |
| | ELECTRICAL PLAN EXAMINER |
| | 561-805-6713 |
| | [email protected] |
| | |