2016-11-23 14:03:03JOB PERMIT NUMBER: 16090649
 JOB ADDRESS: 444 BUNKER RD
 WEST PALM BEACH FLORIDA (COMMERCIAL SOLAR SYSTEM)
 DATE: NOVEMBER 23, 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH NEC
 2011, (NATIONAL ELECTRICAL CODE) AND FBC 2014, (FLORIDA
 BUILDING CODE) AS WELL AS THE CITY OF WEST PALM BEACH
 AMENDMENTS. SEE BELOW A LIST OF ITEMS NOTED.
  
 1] PLANS REQUIRE SIGNING & SEALING BY AN ELECTRICAL
 ENGINEER IN ACCORDANCE WITH FS 471
  
 2] PROVIDE FPL AVAILABLE FAULT CURRENT LETTER & SHOW
 AIC CALCULATIONS TO VERIFY SHORT CIRCUIT RATINGS OF
 ELECTRICAL EQUIPMENT. NEC 110.24, 110.10, 110.9
  
 3] SUBMITTAL DOCUMENTS SHALL BE SUBMITTED IN TWO OR
 MORE SETS WITH EACH PERMIT APPLICATION. FBC 107
  
 4] PLEASE COMPLY WITH GROUNDING & BONDING PROVISIONS
 PER NEC 250.24, 250.28, 250.30. VERIFY GROUNDED
 CONDUCTOR IS'T ATTACHED TO ENCLOSURES ON LOAD SIDE
 CONNECTIONS, VERIFY EQUIPMENT GROUNDING CONDUCTOR
 SYSTEM IS IN PLACE TO CREATE AN EFFECTIVE GROUND
 CURRENT PATH, LASTLY VERIFY SEPARATELY DERIVED SYSTEMS
 IS PROPERLY GROUNDED WITH AN ELECTRODE & BONDED AS TO
 PREVENT OBJECTIONABLE CURRENT.
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED ITEMS. WHEN RESUBMITTING, FOR A QUICKER
 RETURN ON YOUR RE-SUBMITTAL, PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM. CLOUDING THE CHANGES
 WILL BE GREATLY APPRECIATED. IF YOU HAVE FURTHER
 QUESTIONS, PLEASE DON'T HESITATE TO CONTACT ME
 DIRECTLY.
  