Plan Review Notes
Plan Review Notes For Permit 16090638
Permit Number 16090638
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2017-01-06 14:20:501401 CLARE AVENUE
 PERMIT #16090638
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SPOKE WITH JOHN AT GS&P (01/11/17 @12:50PM) AND AGREED
 TO PASS THE PLAN SUBJECT TO THE FOLLOWING ISSUES BEING
 CORRECTED IN A FUTURE REVISION BEFORE A CO IS ISSUED:
  
 SHEET C2.1: RECOMMEND OPTION 5 BELOW FOR THE FIRE
 BACKFLOW PREVENTER:
 PER NFPA 24 SECTION 6.2.1, ALL CONNECTIONS TO PRIVATE
 FIRE SERVICE MAINS FOR FIRE PROTECTION SYSTEMS SHALL BE
 ARRANGED IN ACCORDANCE WITH ONE OF THE FOLLOWING SO
 THAT THEY CAN BE ISOLATED:
 (1)A POST INDICATOR VALVE INSTALLED NOT LESS THAN 40
 FEET FROM THE BUILDING.
 (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A POST
 INDICATOR VALVE SHALL BE PERMITTED TO BE INSTALLED
 CLOSER THAN 40 FEET BUT AT LEAST AS FAR FROM THE
 BUILDING AS THE HEIGHT OF THE WALL FACING THE POST
 INDICATOR VALVE.
 (2) A WALL POST INDICATOR VALVE
 (3) AN INDICATING VALVE IN A PIT, INSTALLED IN
 ACCORDANCE WITH SECTION 6.4
 (4) A BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING
 VALVE NOT LESS THAN 40 FEET FROM THE BUILDING.
 (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A
 BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING VALVE
 SHALL BE PERMITTED TO BE INSTALLED CLOSER THAN 40 FEET
 BUT AT LEAST AS FAR FROM THE BUILDING AS THE HEIGHT OF
 THE WALL FACING THE BACKFLOW PREVENTER.
 (5) CONTROL VALVES INSTALLED IN A FIRE-RATED ROOM
 ACCESSIBLE FROM THE EXTERIOR
 (6) CONTROL VALVES IN A FIRE-RATED STAIR ENCLOSURE
 ACCESSIBLE FROM THE EXTERIOR AS PERMITTED BY THE
 AUTHORITY HAVING JURISDICTION
  
 SHEET M18.0: COMMERCIAL COOKING EXHAUST : PLAN
 INDICATES GREASE DUCT EXHAUSTS MOUNTED TO WEST FACE OF
 BUILDING WALL AND DISCHARGING 10 FEET FROM THE PROPERTY
 LINE; HOWEVER, CIVIL PLAN C2.1 INDICATES THAT THE WEST
 WALL OF THE BUILDING IS VIRTUALLY LOCATED ON THE
 PROPERTY LINE.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved