Plan Review Notes
Plan Review Notes For Permit 16090638
Permit Number 16090638
Review Stop B
Sequence Number 3
Notes
Date Text
2017-01-19 08:20:38****PROVISOS****
 ****ISSUED AT APPLICANT'S RISK****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC 5TH EDITION, BUILDING
  
 1. FBC 503.1, FBC EXISTING BUILDING 1012.5; COMPLIANCE
 NOT CLEAR; REVISE PAGE.
 REFER TO EMAILS; MOST STRINGENT OCCUPANCY WAS NOT
 UTILIZED, INCREASE FOR 1 STORY RATHER THAN 2 STORY
 USED. OPTIONS ARE: SEPARATED USE, NON SEPARATED MIXED
 USE SHOWING COMPLIANCE FOR A3, USE FRONTAGE INCREASE,
 DIFFERENT BUILDING TYPE - IT APPEARS THAT BUILDING
 COMPLIES; A REVISION IS REQUIRED, ISSUED AT APPLICANT'S
 RISK
  
 2. FBC 1006, MEANS OF EGRESS ILLUMINATION, REAR EXIT,
 REQUIRES ILLUMINATION IN THE EXIT DISCHARGE TO THE
 PUBLIC WAY.
 ILLUMINATION NOT SHOWN BUT IS REQUIRED. SITE LIGHTING
 IS UNDER A SEPARATE PERMIT AND SHOULD INCLUDE
 PHOTOMETRICS TO SHOW COMPLIANCE. THIS MAY BE EITHER
 DEMONSTRATED VIA A REVISION, SITE LIGHTING PERMIT, OR
 FIELD VERIFIED BY THE INSPECTOR.
  
 4. FBC ACCESSIBILITY 405.6, RAMP RISE NOT TO EXCEED 30
 INCHES.
 THE DETAIL ON A 2.0.1 SHOWS A RISE OF 33". THIS ITEM
 HAS BEEN REDLINED. THE RISE LIMITATION OF 30" WILL BE
 FIELD VERIFIED BY THE INSPECTOR. IF A SIGNIFICANT
 DESIGN CHANGE IS REQUIRED, A REVISION IS REQUIRED.
  
 5. CHECK OUT AISLES, SALES AND SERVICE COUNTERS, TO
 COMPLY WITH FBC ACCESSIBILITY 904.
  
 6. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB, FBC
 109.
  
 FLOOD / NFIP PROVISO:
  
 ABBREVIATIONS USED (SEE ALSO FBC 1612):
  
 BFE, BASE FLOOD ELEVATION
 DFE, DESIGN FLOOD ELEVATION (BFE PLUS FREEBOARD AND
 OTHER REQUIREMENTS)
 FFE, FINISHED FLOOR ELEVATION
 FIRM, FLOOD INSURANCE RATE MAP
 SFHA, SPECIAL FLOOD HAZARD AREA
  
 THIS STRUCTURE IS LOCATED IN SFHA ZONE A8, BFE 13 FEET
 NGVD29 PER FIRM. BASED ON PROJECT VALUE AND PROPERTY
 APPRAISER VALUE OF THE STRUCTURE, THIS IS CONSIDERED A
 SUBSTANTIAL IMPROVEMENT.
  
 PRIOR TO CONCRETE POUR, A FORM BOARD SURVEY WITH
 ELEVATIONS WILL BE REQUIRED. ALL IMPROVEMENTS ARE TO BE
 AT OR ABOVE DFE OR BE DESIGNED TO RESIST FLOOD LOADS,
 FBC 1612.
  
 7. PROVISO, PRIOR TO FINAL INSPECTION, THE FOLLOWING IS
 TO BE SUBMITTED:
  
 A. COMPLETED ELEVATION CERTIFICATE. ALL EQUIPMENT AND
 IMPROVEMENTS TO BE ABOVE DFE (14 FEET NGVD29).
 B. PHOTOGRAPHS OF ALL SIDES OF THE STRUCTURE
 C. PHOTOGRAPHS OF ALL MECHANICAL AND UTILITY EQUIPMENT
 LOCATED OUTSIDE THE BUILDING SHOWING ITS RELATION TO
 THE BUILDING AND GROUND AND ITS REQUIRED ANCHORING.
  
 NOTE THAT ROOFTOP EQUIPMENT IS NOT EXEMPTED FROM
 PHOTOGRAPH REQUIREMENTS.
  
 THESE REQUIREMENTS ARE FROM CRS ACTIVITY RA3 TO
 DOCUMENT COMPLIANCE WITH FBC 1612.
  
  