| 2016-12-09 10:55:29 | ****PROVISO**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | ABBREVIATIONS USED (SEE ALSO FBC 1612): |
| | |
| | BFE, BASE FLOOD ELEVATION |
| | DFE, DESIGN FLOOD ELEVATION (BFE PLUS FREEBOARD AND |
| | OTHER REQUIREMENTS) |
| | FFE, FINISHED FLOOR ELEVATION |
| | FIRM, FLOOD INSURANCE RATE MAP |
| | SFHA, SPECIAL FLOOD HAZARD AREA |
| | |
| | THIS STRUCTURE IS LOCATED IN SFHA ZONE A8, BFE 13 FEET |
| | NGVD29 PER FIRM. BASED ON PROJECT VALUE AND PROPERTY |
| | APPRAISER VALUE OF THE STRUCTURE, THIS IS CONSIDERED A |
| | SUBSTANTIAL IMPROVEMENT. |
| | |
| | PROPERTY APPRAISER PROPOSED 2016 VALUE FOR STRUCTURE, |
| | $480,558 |
| | VALUE OF IMPROVEMENT, $1,000,000 |
| | |
| | BASED ON THE SURVEY PROVIDED (MILLER SURVEYING DEC 23, |
| | 2015) THE FINISHED FLOOR FOR THIS BUILDING IS 18.20, |
| | WHICH COMPLIES WITH THE MINIMUM DFE WHICH APPEARS TO BE |
| | 14 FT NGVD29. |
| | |
| | PRIOR TO CONCRETE POUR, A FORM BOARD SURVEY WITH |
| | ELEVATIONS WILL BE REQUIRED. ALL IMPROVEMENTS ARE TO BE |
| | AT OR ABOVE DFE OR BE DESIGNED TO RESIST FLOOD LOADS, |
| | FBC 1612. |
| | |
| | 7. PROVISO, PRIOR TO FINAL INSPECTION, THE FOLLOWING IS |
| | TO BE SUBMITTED: |
| | |
| | A. COMPLETED ELEVATION CERTIFICATE. ALL EQUIPMENT AND |
| | IMPROVEMENTS TO BE ABOVE DFE (14 FEET NGVD29). |
| | B. PHOTOGRAPHS OF ALL SIDES OF THE STRUCTURE |
| | C. PHOTOGRAPHS OF ALL MECHANICAL AND UTILITY EQUIPMENT |
| | LOCATED OUTSIDE THE BUILDING SHOWING ITS RELATION TO |
| | THE BUILDING AND GROUND AND ITS REQUIRED ANCHORING. |
| | |
| | NOTE THAT ROOFTOP EQUIPMENT IS NOT EXEMPTED FROM |
| | PHOTOGRAPH REQUIREMENTS. |
| | |
| | THESE REQUIREMENTS ARE FROM CRS ACTIVITY RA3 TO |
| | DOCUMENT COMPLIANCE WITH FBC 1612. |
| | |
| | |
| | |