| 2016-12-01 11:49:18 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) REPEAT OF COMMENT 6: |
| | |
| | THE PROPOSED REMODEL APPEARS TO ALTER 50 OR MORE |
| | AUTOMATIC FIRE SPRINKLERS. |
| | |
| | PER FL BLDG CODE 105.3..1.2(2) |
| | |
| | 2. FIRE SPRINKLER DOCUMENTS FOR ANY NEW BUILDING OR |
| | ADDITION WHICH INCLUDES A FIRE SPRINKLER SYSTEM WHICH |
| | CONTAINS 50 OR MORE SPRINKLER HEADS. PERSONNEL AS |
| | AUTHORIZED BY CHAPTER 633 FLORIDA STATUTES, MAY DESIGN |
| | A FIRE SPRINKLER SYSTEM OF 49 OR FEWER HEADS AND MAY |
| | DESIGN THE ALTERATION OF AN EXISTING FIRE SPRINKLER |
| | SYSTEM IF THE ALTERATION CONSISTS OF THE RELOCATION, |
| | ADDITION OR DELETION OF NOT MORE THAN 49 HEADS, |
| | NOTWITHSTANDING THE SIZE OF THE EXISTING FIRE SPRINKLER |
| | SYSTEM. |
| | |
| | |
| | NO FIRE PROTECTION DOCUMENTS HAVE BEEN SUBMITTED. THE |
| | FUTURE SUBMITTAL OF SHOP DRAWINGS WILL NOT MEET THE |
| | REQUIREMENTS OF THE BLDG CODE OR FAC. |
| | |
| | PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, |
| | FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE |
| | POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF |
| | APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, |
| | CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR |
| | AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER |
| | SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) |
| | AND ANY PERFORMANCE BASED INFORMATION SUCH AS |
| | PRE-ENGINEERED SYSTEMS. |
| | |
| | THE MASTER PLAN SUBMITTAL (THIS SUBMITTAL) SHALL |
| | INCLUDE ALL OF THE REQUIRED ELEMENTS OF THE ABOVE NOTED |
| | FAC EITHER IN WRITTEN NARRATIVE OR DRAWING FORMAT, |
| | SIGNED AND SEALED BY THE EOC. SHOP DRAWINGS SHALL THEN |
| | BE PREPARED AND SUBMITTED BASED ON THE EOR CRITERIA AT |
| | THE APPLICBALE TIME UNDER SEPARATE PERMIT SUBMITTAL. |
| | |
| | PLEASE PROVIDE THE REQUIRED DOCUMENTATION WITH THIS |
| | PERMIT. |
| | |
| | |
| | |
| | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |