| 2016-10-19 16:10:11 | 1ST REVIEW |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER LL |
| | CITY OF WEST PALM BEACH |
| | DEVELOPMENT SERVICES |
| | BUILDING DIVISION |
| | 561-805-6711 |
| | [email protected] |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. PLEASE SHOW DEPTH OF SHOWER SHALL COMPLY WITH FBC |
| | ACC 608.2.2 |
| | |
| | 2. SHOW CLEAR FLOW SPACE FOR SHOWER SHALL COMPLY WITH |
| | FBC ACC 608.2.2.1 |
| | |
| | 3. PLEASE SHOW THE END OF THE GRAB BARS IN SHOWER 6IN. |
| | FROM ADJACENT WALLS PER FBC ACC 608.3.2 |
| | |
| | 4. PLEASE INDICATE WITCH WALL SHOWER CONTROLS WILL BE |
| | LOCATED AND SHOW COMPLIANCE WITH FBC ACC 608.5.2 |
| | |
| | 5. DOR SWING IN BATHROOMS SHALL COMPLY WITHE FBC ACC |
| | 603.2.3 DOOR SWING. |
| | DOORS SHALL NOT SWING INTO THE CLEAR FLOOR SPACE OR |
| | CLEARANCE REQUIRED FOR ANY FIXTURE. DOORS SHALL BE |
| | PERMITTED TO SWING INTO THE REQUIRED TURNING SPACE. |
| | |
| | 6. A SEPARATE PERMIT IS REQUIRED FOR BACK FLOW.PER WPB |
| | UTILITIES DEPT. |
| | |
| | 7. THE DFU STATED ON BUILDING SEWER APPEARS LOW PLEASE |
| | PROVIDE CALCULATIONS PER FBC PL SEC 709 AND INDICATE ON |
| | THE PLAN THE SLOPE OF THE PIPE. SHALL COMPLY WITH FBC |
| | PL TABLE 710.1(1) |
| | |
| | 8. THE FLOOR SINKS THAT ARE SERVING DELI OR DISPLAY |
| | CASES SUCH AS IN RM 107, 108 SHALL HAVE TRAP PRIMERS |
| | PER FBC PL 1002.4 |
| | |
| | 9. PLEASE PROVIDE A OCCUPANT LOAD BREAKDOWN BY AREA AND |
| | ROOM. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 10. IF YOU ARE SERVING FOOD AND DRINKS TO THE PUBLIC |
| | FOR CONSUMPTION ON THE PROPERTY IT SHALL BE CLASSIFIED |
| | AS AN A2 NOT AN M OCCUPANCY. PER FBC 303.3 ASSEMBLY |
| | GROUP A-2. |
| | ASSEMBLY USES INTENDED FOR FOOD AND/OR DRINK |
| | CONSUMPTION INCLUDING, BUT NOT LIMITED TO: |
| | |
| | BANQUET HALLS |
| | |
| | CASINOS (GAMING AREAS) |
| | |
| | NIGHTCLUBS |
| | |
| | RESTAURANTS, CAFETERIAS AND SIMILAR DINING FACILITIES |
| | (INCLUDING ASSOCIATED COMMERCIAL KITCHENS) |
| | |
| | TAVERNS AND BARS |
| | |
| | 11. IS THER GOING TO BE SEATING ANYWHERE SUCH AS THE |
| | PATIOS OR HALL AREAS PLEASE CLARIFY. PER WPB AMEND TO |
| | FBC 107.2.1 |
| | |
| | 12. IT APPEARS THAT THE MAIN BATHROOM IS COMBINED |
| | BATHROOM GROUP FOR BOTH SEX. BATHROOMS SHALL COMPLY |
| | WITH . FBC PL 403.2 SEPARATE FACILITIES. |
| | WHERE PLUMBING FIXTURES ARE REQUIRED, SEPARATE |
| | FACILITIES SHALL BE PROVIDED FOR EACH SEX. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |