| 2016-09-28 09:02:16 | 1ST REVIEW FBC-2014 MECHANICAL |
| | PERMIT #16090638 |
| | 9/28/16 |
| | |
| | 1) SEPARATE PERMITS AND PLANS ARE REQUIRED FOR KITCHEN |
| | EXHAUST HOODS, FIRE SUPRESSION SYSTEMS, AND WALK-IN |
| | COOLERS AND FREEZERS. PLEASE PLACE A NOTE ON THE PLAN |
| | IN BOLD LETTERS. |
| | |
| | 2) PROVIDE MINIMUM VENTILATION CALCULATIONS ON THE PLAN |
| | PER TABLE 403.3. PROVIDE A SCHEDULE OR TABLE THAT SHOWS |
| | THE REQUIRED AND PROVIDED CFMS OF O/A. |
| | |
| | 3) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE |
| | GAS-FIRED COOKING APPLIANCE- SECTION 304 FBC-14 FUEL |
| | GAS. |
| | |
| | 4) PROVIDE INSTALLATION DETAILS FOR THE AHU'S. |
| | |
| | 5) PROVIDE PRIMARY AND SECONDARY CONDENSATE DISPOSAL |
| | DETAILS FOR THE AHU'S- SECTION 307. SHOW THE PRIMARY |
| | PIPING RUNS AND DISCHARGE LOCATIONS. |
| | |
| | 6) THE PLAN DESIGNATES ONE TENANT ROOM AS A BAKERY, |
| | HOWEVER NO BAKING OVENS ARE SHOWN IN THE SCHEDULES- |
| | PLEASE REVIEW AND VERIFY NO BAKING TO BE DONE IN THE |
| | ROOM. |
| | |
| | 7) SHEET M2.0: TRANSFERRED AIR FROM THE FOOD PREP 104 |
| | TO THE HALL 100 IS PROHIBITED PER SECTION 601.2. THE |
| | LOCATION OF THE GRILL IN THE ROOM IS ALSO NOT IN |
| | COMPLIANCE WITH SECTION 918.6. |
| | |
| | 8) M3.0: TRANSFERRED AIR FROM THE STORAGE 119 TO THE |
| | CORRIDOR 120 IS PROHIBITED- SECTION 601.2. |
| | |
| | 9) SOME OF THE RETURN GRILLS FOR THE AHU'S APPEAR |
| | UNDERSIZED FOR THE AMOUNT OF CFMS BEING RETURNED. |
| | PLEASE INDICATE WHAT CALULATION METHODOLOGY IS BEING |
| | USED FOR SIZING THE GRILLS. |
| | |
| | 10) PROVIDE A MECHANICAL ROOF PLAN SHOWING ALL REQUIRED |
| | CLEARANCE DISTANCE MEASUREMENTS FROM AIR INTAKES TO |
| | EXHAUST OUTLETS, AND FROM EQUIPMENT TO ROOF EDGES. |
| | |
| | 11) SUBMIT THE NOA'S LISTED ON THE PLANS FOR THE ROOF |
| | STANDS AND LOUVERS WITH SHOP DRAWING APPROVAL |
| | SIGNATURES. PLEASE HIGHLIGHT, CIRCLE, OR OTHERWISE MARK |
| | ALL APPLICABLE INSTALLATION DETAILS, NOTES, DESIGN |
| | PRESSURES, ETC. ON THE ROOF STAND NOA. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 561-805-6719 |