| Plan Review Notes For Permit 16090628 |
| Permit Number |
16090628 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-09-19 12:26:38 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | PASSED WITH THE FOLLOWING PROVISO'S | | | | | | 1] FPL LETTER REQUIRED ON-SITE FOR FIELD INSPECTOR | | | REVIEW. INFORMATION NEEDED TO VERIFY MINIMUM AIC & | | | SHORT CIRCUIT RATINGS, PLANS DIDN'T INCLUDE TRANSFORMER | | | SECONDARY IMPEDIANCE. | | | | | | 2] PROVIDE A SWITCHED CONTROLLED LIGHTING OUTLET BY THE | | | ATTIC ENTRANCE LOCATED NEAR ANY EQUIPMENT REQUIRING | | | SERVICING. NEC 210.70(3) | | | | | | 3] INSTALL AN INTERSYSTEM BONDING TERMINAL. NEC 250.94 | | | |
|