| Plan Review Notes For Permit 16090627 |
| Permit Number |
16090627 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-09-19 10:53:56 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | 1] CLARIFY "EXISTING TO NEW" SERVICE RISER-DIAGRAM | | | CONFIGURATION. SPECIFY WIRE & CONDUIT SIZES, GROUNDING | | | DETAIL TO SHOW BONDING TO WATER PIPE, OR METAL OF | | | BUILDING. FBC 107.3.5.3 | | | | | | 2] PROVIDE A DOUBLE POLE SWITCH DISCONNECT WITHIN SIGHT | | | OF THE MINI-SPLIT AND LABEL EXTERIOR OUTLET GFCI | | | "WR/WP". FBC-R_E4101.5 & FBC-R_E4002.10 | | | | | | 3] ADD A NOTE FOR SMOKE ALARMS PER FBC-R 314 & 315 | | | | | | 4] ADD A NOTE FOR TAMPER-RESISTANT RECEPTACLES PER | | | FBC-R_E4002.14 |
|