| Date |
Text |
| 2016-10-24 11:33:39 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) FBC ENERGY CONSERVATION - SECT. 103.1.1.2 CODE |
| | COMPLIANCE CERTIFICATION. |
| | THE BUILDING'S OWNER, THE OWNER'S ARCHITECT, OR OTHER |
| | AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL |
| | CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH THE |
| | CODE, AS PER SECTION 553.907, FLORIDA STATUTES, PRIOR |
| | TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR |
| | RENOVATION. FBC ENERGY CONSERVATION SECTIONS |
| | R101.5.1.1.1 OR R101.5.1.1.2. SUBMIT TWO SETS OF ENERGY |
| | COMPLIANCE FORMS AS REQUIRED. |
| | |
| | 2) THE SOIL REPORT THAT WAS SUBMITTED FROM ALLTERRA |
| | ENGINEERING & TESTING STATES THAT A 24 INCH WIDE |
| | CONTINOUS FOOTING IS REQUIRED TO ACHIEVE A 2500 PSF |
| | ALLOWABLE BEARING PRESSURE. THE PLANS SHOW AN 18" WIDE |
| | MONOLITHIC FOOTING. PLEASE REVIEW THE REPORT TO INSURE |
| | THAT THE PROPOSED FOOTING WILL BE ADEQUATE. FBC 107.2.1 |
| | |
| | 3) PROVIDE A LINTEL SCHEDULE ON THE PLANS. FBC 107.2.1 |
| | |
| | 4) SHOW COMPLIANCE WITH FBC - R905.2.2 SLOPE. ASPHALT |
| | SHINGLES SHALL ONLY BE USED ON ROOF SLOPES OF TWO UNITS |
| | VERTICAL IN 12 UNITS HORIZONTAL (2:12) OR GREATER. FOR |
| | ROOF SLOPES FROM TWO UNITS VERTICAL IN 12 UNITS |
| | HORIZONTAL (2:12) UP TO FOUR UNITS VERTICAL IN 12 UNITS |
| | HORIZONTAL (4:12), TWO LAYERS OF UNDERLAYMENT COMPLYING |
| | WITH ASTM D 226, TYPE I OR TYPE II, ASTM D 4869, TYPE I |
| | OR TYPE II OR ASTM D 6757 IS REQUIRED IN ACCORDANCE |
| | WITH SECTION R905.2.7. |
| | |
| | 5) FBC R403.1.4 REQUIRES EXTERIOR FOOTINGS TO BE A |
| | MINIMUM OF 12 INCHES BELOW GRADE. SECTION B ON SHEET 5 |
| | SHOWS A 16" THICK FOOTING WITH 8" ABOVE GRADE WHICH |
| | LEAVES ONLY 8" BELOW GRADE. |
| | |
| | 6) THE PRODUCT APPROVALS FOR THE GAF ASPHALT SHINGLES |
| | MIAMI DADE NOA NO. 14-1022.16 ARE MISSING SOME PAGES |
| | AND THE ONES THAT WERE SUBMITTED ARE MISSING |
| | INFORMATION AT THE BOTTOM OF THE PAGES. SUBMIT COMPLETE |
| | PRODUCT APPROVALS. FBC 107.2.1 |
| | |
| | 7) THE PRODUCT APPROVALS FOR THE YALE OGRON FRENCH |
| | DOORS ARE MISSING SOME PAGES AND THE ONES THAT WERE |
| | SUBMITTED ARE MISSING INFORMATION AT THE BOTTOM AND |
| | SIDES OF THE PAGES. SUBMIT COMPLETE PRODUCT APPROVALS. |
| | FBC 107.2.1 |
| | |
| | 8) TWO SETS OF PRODUCT APPROVALS ARE REQUIRED PER FBC |
| | 107.1. SUBMIT AN ADDITIONAL SET OF PRODUCT APPROVALS |
| | FOR THE CUSTOM WINDOW SYSTEMS INC. SINGLE HUNG WINDOWS, |
| | FL15699-R2. |
| | |
| | 9) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A |
| | RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| | COMMENTS HAS BEEN ADDRESSED. |
| | |
| | |
| | |
| | |
| | |
| | |