| Notes |
| Date |
Text |
| 2016-11-02 15:33:44 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #16090626 | | | 11/2/16 | | | | | | COMMENTS FROM THE 1ST REVIEW STILL EXIST. I AM | | | REPRINTING THEM BELOW WITH SOME ADDITIONAL REVIEW | | | NOTES. | | | | | | 1) PLEASE PROVIDE THE FOLLOWING: A) REFRIGERATION | | | EQUIPMENT SCHEDULES. B) LOCATIONS OF REFRIGERATION | | | EQUIPMENT AND REFRIGERANT PIPING RUNS AND PIPE DETAILS. | | | C) EVAPORATOR CONDENSATE DISPOSAL DETAILS. D) WIND LOAD | | | ENGINEERING FOR INSTALLATION OF THE WALK-IN BOXES AND | | | THE EXTERIOR CONDENSER. | | | | | | 2) THE UPLOADED SUBMITTAL FROM PFS CORPORATION | | | INDICATES THAT THE WALK-IN COOLER HAS BEEN APPROVED IN | | | ACCORDANCE WITH SECTION 61G20-3 FAC FOR PRODUCT | | | APPROVAL. PLEASE PROVIDE A COPY OF THE PRODUCT | | | APPROVAL. | | | | | | 3) THE UPLOADED K-3 PLAN SHEET REQUIRES AN ELECTRONIC | | | SIGNATURE AND SEAL FROM THE ARCHITECT OF RECORD ANDREW | | | N. SHARE- SEE SECTION 61G1-16.005 FAC | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|