Plan Review Notes
Plan Review Notes For Permit 16090626
Permit Number 16090626
Review Stop B
Sequence Number 2
Notes
Date Text
2016-12-30 06:45:38BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16090626
 ADD: 1721 PALM BEACH LAKES BLVD. SUITE # E419
 CONT: AIR SOUTH MECHANICAL INC.
 TEL: 305-828-9400
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW.
 DATE: FRI. DEC. 30/ 2016
 ACTION: DENIED
  
 1) PLEASE NOTE THE 1ST REVIEW WAS PASSED BELIEVING THIS
 TO BE A INDOOR COOLER/ FREEZER, THIS IS NOT THE CASE.
 IT APPEARS THAT INTERNATIONAL CODE STORAGE HAS HAD
 TESTING COMPLETED AND REVIEWED BY THE STATE OF FLORIDA
 FOR A STATEWIDE PRODUCT APPROVAL. PLEASE NOTE TO DATE
 NO FLORIDA COVERSHEET HAS BEEN PROVIDED WITH A CURRENT
 FLORIDA APPROVAL NUMBER. IF GOING THROUGH THE PROCESS
 AND NOT AFFIRMED BY THE STATE THEN LET US KNOW WE CAN
 E-MAIL THE FORMS FOR A LOCAL PRODUCT APPROVAL. THE CITY
 OF WEST PALM BEACH USES THE SAME 10 CRITERIA AS THE
 STATE BUT MUST BE SUBMITTED ON THE CITY FORMS FOR
 REVIEW BY THE BUILDING OFFICIAL.
 2014 FBC-B 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA
 ADMINISTRATIVE CODE 61G20-3.004 OPTIONAL STATEWIDE
 APPROVAL. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE
 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)((G) EXTERIOR COOLER& FREEZERS.
  
 2) SHEET K-3 DOES NOT PROVIDE WHO IS THE DESIGNER OF
 RECORD FOR THIS SHEET. IN THE TITLE BLOCK THERE IS NO
 DESIGNERS NAME TAKING RESPONSIBILITY FOR THE DESIGN. IT
 WOULD APPEAR THAT INTERNATIONAL COLD STORAGE IS THE
 DESIGNER. 2014 FLORIDA BUILDING CODE W 2014 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION 107.3.4 DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE.
  
 3) SHEET K-3 IN THE CENTER OF THE SHEET THERE IS THE
 WIND DESIGN CRITERIA. UNDER THE HEADINGCOMPONENTS AND
 CLADDING ULTIMATE WIND.
 PRESSURES WALL ARE IN VULT. PLEASE CONVERT TO VASD
 SINCE ALL PRODUCT APPROVALS ARE IN VASD.
 ROOF PRESSURES DO NOT PROVIDE THE SQAURE FOOT AREA
 THESE PRESSURES WERE TAKEN FOR? FOR THE COMPONENTS AND
 CLADDING THE SQUARE FOOT AREA IS UASULLY TAKEN FOR THE
 FASTENERS OR 10 SQ. FT. IT ALSO APPEARS THEY ARE IN
 VULT, PLEASE ALSO PROVIDE IN VASD SINCE ALL PRODUCT
 APPROVALS ARE IN VASD. 1609.3.1 WIND SPEED CONVERSION.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  