2016-09-29 12:24:361ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16090626
 9/29/16
  
 1) BECAUSE THE WALK-IN COOLER AND FREEZER ARE BEING
 PERMITTED SEPARATELY FROM THE MAIN RESTAURANT
 OCCUPANCY, COMPLETE PLANS AND DETAILS ARE REQUIRED-
 ONLY ONE PLAN SHEET WAS EXPORTED FROM THE MAIN SETS.
 PLEASE PROVIDE THE FOLLOWING: A) REFRIGERATION
 EQUIPMENT SCHEDULES. B) LOCATIONS OF REFRIGERATION
 EQUIPMENT AND REFRIGERANT PIPING RUNS AND PIPE DETAILS.
 C) EVAPORATOR
  
 CONDENSATE DISPOSAL DETAILS. D) WIND LOAD ENGINEERING
 FOR INSTALLATION OF THE WALK-IN BOXES AND THE EXTERIOR
 CONDENSER.
  
 2) PLEASE NOTE THAT THE EXTERIOR WALK-IN BOXES WILL
 REQUIRE A STRUCTURAL REVIEW.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER