| Plan Review Notes For Permit 16090626 |
| Permit Number |
16090626 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-09-29 12:24:36 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #16090626 | | | 9/29/16 | | | | | | 1) BECAUSE THE WALK-IN COOLER AND FREEZER ARE BEING | | | PERMITTED SEPARATELY FROM THE MAIN RESTAURANT | | | OCCUPANCY, COMPLETE PLANS AND DETAILS ARE REQUIRED- | | | ONLY ONE PLAN SHEET WAS EXPORTED FROM THE MAIN SETS. | | | PLEASE PROVIDE THE FOLLOWING: A) REFRIGERATION | | | EQUIPMENT SCHEDULES. B) LOCATIONS OF REFRIGERATION | | | EQUIPMENT AND REFRIGERANT PIPING RUNS AND PIPE DETAILS. | | | C) EVAPORATOR | | | | | | CONDENSATE DISPOSAL DETAILS. D) WIND LOAD ENGINEERING | | | FOR INSTALLATION OF THE WALK-IN BOXES AND THE EXTERIOR | | | CONDENSER. | | | | | | 2) PLEASE NOTE THAT THE EXTERIOR WALK-IN BOXES WILL | | | REQUIRE A STRUCTURAL REVIEW. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|