| 2016-09-26 08:30:10 | INITIAL ELECTRICAL PLAN REVIEW |
| | |
| | APPLICABLE CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70- 2011 |
| | COMMENTS: |
| | |
| | 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE |
| | PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE |
| | PERMITS AND DATA CUT SHEET SUBMITTALS FOR ALL SITE |
| | LIGHTING AND ASSOCIATED EQUIPMENT, ALL LOW VOLTAGE |
| | SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE ALARM, |
| | ACCESS CONTROLS, CCTV, PHONE AND DATA, SIGNAGE, |
| | WIRELESS SYSTEM, ETC. A NOTE WILL SUFFICE. |
| | 2. PLEASE ADD A GENERAL NOTE TO SHEETS TO INDICATE THE |
| | REQUIREMENTS OF NEC 300.5D3 AND TABLE 300.5 FOR MINIMUM |
| | COVER REQUIREMENTS FOR CONDUITS AND THE PLACEMENT OF A |
| | WARNING RIBBON FOR THE SERVICE LATERAL CONDUCTORS SHOWN |
| | FOR THIS PROJECT. A NOTE WILL SUFFICE |
| | 3. ADD A NOTE TO MAINTAIN ALL ELECTRICAL EQUIPMENT |
| | ABOVE THE BASELINE FLOOD ELEVATION PER STATE AND CITY |
| | REGULATORY AGENCIES. |
| | 4. PLEASE PROVIDE AVAILABLE FAULT CURRENT AVAILABLE AT |
| | THE FPL SERVICE. ATTACH TO DOCUMENTS LETTER FROM |
| | FLORIDA POWER & LIGHT INDICATING AIC. SHOW AIC |
| | CALCULATION BASED ON INFORMATION PROVIDED BY UTILITY |
| | FOR APPROVAL. NEC 110.24 FBC 107 |
| | 5. PROVIDE LIGHTING DENSITIES PER FLORIDA BUILDING CODE |
| | ENERGY CONSERVATION 2014 5TH EDITION |
| | 6. PLEASE ADDRESS FIRE COMMENTS RELATED TO THE |
| | ELECTRICAL SCOPE OF WORK. |
| | 7. CLARIFY IF THIS IS A SHELL PERMIT, ITEMS MARKED AS |
| | FUTURE INSTALL (SUBJECT TO BUILDING REVIEW)? |
| | 8. SHOW AN INTERSYSTEM BONDING TERMINAL AT THE SERVICE |
| | PER NEC 250.94 |
| | 9. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE |
| | TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING |
| | THIS PROJECT. |
| | |
| | |