2016-09-21 11:06:351ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16090579
 9/21/16
  
 1) SHEET M6.1: THE AIR CHANGES SCHEDULE INDICATES IV
 ROOMS EAST AND WEST, HOWEVER THE FLOOR PLAN SHOWS ONLY
 ONE IV "PREP" ROOM ON THE EAST END- SEE SHEET A001.
 PLEASE NOTE THE ROOM IS LABELED IV ROOM 108 ON M2.1.
  
 2) M6.1: INDICATE WHICH CODE STANDARD WAS USED TO
 DETERMINE THE REQUIRED AIR CHANGES PER HOUR FOR THE IV
 ROOM.
  
 3) SUBMIT SPECS FOR THE 2X4 FAN FILTER UNITS IN THE
 CEILING WITH SHOP DRAWING APPROVAL SIGNATURES BY THE
 DESIGN PROFESSIONAL OF RECORD. THE FILTERS SHALL BE IN
 COMPLIANCE WITH TABLE 6-1 ASHRAE 170-2008.
  
 4) REFER TO TABLE 7-1 ASHRAE 170-2008 AND PROVIDE THE
 VENTILATION DESIGN PARARMETERS FOR ALL ROOMS AND SPACES
 IN THE NEW IV AREA. SEE SECTION 6.7.1 AND PROVIDE
 DUCTED RETURNS IF APPLICABLE PER TABLE 7-1.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719