| Plan Review Notes For Permit 16090579 |
| Permit Number |
16090579 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-09-21 11:06:35 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #16090579 | | | 9/21/16 | | | | | | 1) SHEET M6.1: THE AIR CHANGES SCHEDULE INDICATES IV | | | ROOMS EAST AND WEST, HOWEVER THE FLOOR PLAN SHOWS ONLY | | | ONE IV "PREP" ROOM ON THE EAST END- SEE SHEET A001. | | | PLEASE NOTE THE ROOM IS LABELED IV ROOM 108 ON M2.1. | | | | | | 2) M6.1: INDICATE WHICH CODE STANDARD WAS USED TO | | | DETERMINE THE REQUIRED AIR CHANGES PER HOUR FOR THE IV | | | ROOM. | | | | | | 3) SUBMIT SPECS FOR THE 2X4 FAN FILTER UNITS IN THE | | | CEILING WITH SHOP DRAWING APPROVAL SIGNATURES BY THE | | | DESIGN PROFESSIONAL OF RECORD. THE FILTERS SHALL BE IN | | | COMPLIANCE WITH TABLE 6-1 ASHRAE 170-2008. | | | | | | 4) REFER TO TABLE 7-1 ASHRAE 170-2008 AND PROVIDE THE | | | VENTILATION DESIGN PARARMETERS FOR ALL ROOMS AND SPACES | | | IN THE NEW IV AREA. SEE SECTION 6.7.1 AND PROVIDE | | | DUCTED RETURNS IF APPLICABLE PER TABLE 7-1. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|