| 2017-05-24 11:27:12 | 600 OKEECHOBEE BOULEVARD |
| | PERMIT #16090560 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | SECOND REQUEST: NO LISTING SPECIFICATIONS OR |
| | INSTALLATION MANUAL PROVIDED FOR THE PIZZA OVEN OR |
| | WOOD-FIRED GRILL. PER NFPA 1 SECTION 50.6 MINIMUM |
| | SAFETY REQUIREMENTS FOR COOKING EQUIPMENT. COOKING |
| | EQUIPMENT SHALL BE APPROVED BASED ON THE LISTINGS BY A |
| | TESTING LABORATORY. |
| | |
| | PLANS INDICATE THE INSTALLATION OF A WOOD-FIRED GRILL. |
| | PROVIDE EQUIPMENT SPECIFICATIONS. HOW WILL THIS GRILL |
| | BE OPERATED AND PROTECTED IN ACCORDANCE WITH NFPA 96 - |
| | CHAPTER 14: SOLID FUEL COOKING OPERATIONS? SOLID |
| | COOKING OPERATIONS AND DESIGN SHALL COMPLY WITH NFPA |
| | 96. FOR EXAMPLE: PER SECTION 14.9.2.1. FUEL STORAGE |
| | SHALL NOT EXCEED A ONE-DAY SUPPLY WHERE STORAGE IS |
| | LOCATED IN THE SAME ROOM AS THE SOLID FUELED APPLIANCE, |
| | OR IN THE SAME ROOMS AS THE FUEL-LOADING OR CLEAN-OUT |
| | DOORS. SECTION14.9.3.7.3 APPLIANCES WITH FIREBOXES OVER |
| | 5 FT3 THE WATER SOURCE SHALL BE A FIXED PIPE WATER |
| | SYSTEM WITH A HOSE OF ADEQUATE LENGTH TO REACH THE |
| | COMBUSTION AND COOKING CHAMBERS OF THE APPLIANCE. ALL |
| | OVEN ASH SHALL BE REMOVED FROM THE ASH COMPARTMENT AT |
| | LEAST ONCE PER DAY. THE ASH SHALL BE SPRAYED ADEQUATELY |
| | WITH WATER BEFORE REMOVAL TO EXTINGUISH ANY HOT ASH OR |
| | CINDERS AND TO CONTROL THE DUST WHEN THE ASH IS MOVED. |
| | SECTION 14.9.3.8.1 A HEAVY METAL CONTAINER OR CART |
| | (MINIMUM 16 GAUGE) WITH A COVER SHALL BE PROVIDED FOR |
| | THE REMOVAL OF ASH. THE ASH REMOVAL CONTAINER OR CART |
| | SHALL NOT EXCEED A MAXIMUM OF 20 GAL CAPACITY, SHALL BE |
| | ASSIGNED FOR THIS ONE PURPOSE, SHALL BE ABLE TO BE |
| | HANDLED EASILY BY ANY EMPLOYEE ASSIGNED THE TASK, AND |
| | SHALL PASS EASILY THROUGH ANY PASSAGEWAY TO THE OUTSIDE |
| | OF THE BUILDING. THE CONTAINER OR CART SHALL ALWAYS BE |
| | COVERED WHEN IT IS BEING MOVED THROUGH THE PREMISES. |
| | |
| | SHEET A1.3: THE GREASE FILTERS AND GREASE CUP IS |
| | LOCATED MORE THAN 12 FEET ABOVE THE FLOOR. HOW WILL |
| | THIS SPACE BE ACCESSED FOR ROUTINE CLEANING? |
| | |
| | WESLEY JOLIN |
| | ASSISTANT FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |