| 2016-09-22 10:39:30 | 1ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING, |
| | ENERGY CONSERVATION CODES |
| | PERMIT #16090560 |
| | 9/22/16 |
| | |
| | 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE |
| | AND PROVIDE A O/A VENTILATION CALCULATION FOR THE |
| | EXPANDED DINING ROOM AND KITCHEN AREA PER TABLE 403.3 |
| | FBC-14 MECHANICAL. PROVIDE A SCHEDULE THAT INDICATES |
| | THE REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR. |
| | |
| | 2) THE SUBMITTED AC CALCULATIONS INDICATE 100 CFMS OF |
| | OUTDOOR VENTILATION AIR. PLEASE CLARIFY HOW THE AIR IS |
| | BEING PROVIDED TO THE AHU'S- NO O/A DUCTS ARE SHOWN. |
| | |
| | 3) THE SUBMITTED ENERGYGAUGE COMPLIANCE FORM INDICATES |
| | "NEW FINISHED BUILDING" ON PAGE 2. THE PLANS ARE |
| | INDICATING AN EXTENSION OF CONDITIONED SPACE WHICH IS |
| | DEFINED AS AN ADDITION- SEE SECTION 202 FBC-14 ENERGY |
| | CONSERVATION. PLEASE CORRECT THE CALCS. |
| | |
| | 4) PLEASE PLACE A NOTE ON THE PLANS INDICATING SEPARATE |
| | PLANS AND PERMITS ARE REQUIRED FOR THE NEW EXHAUST |
| | HOODS AND FIRE SUPPRESSION SYSTEMS. PLEASE NOTE THAT |
| | THE REQUIREMENT FOR MAKEUP AIR TEMPERATURE WILL BE |
| | REVIEWED UNDER THAT PERMIT- REFER TO SECTION 508.1.1. |
| | |
| | 5) STRUCTURAL DETAILS AND WIND LOAD DESIGN CRITERIA FOR |
| | INSTALLATION OF THE ROOF TOP MECHANICAL EQUIPMENT NOT |
| | PROVIDED- SECTION 301.15. |
| | |