| Notes |
| Date |
Text |
| 2016-09-21 08:48:58 | PLEASE CLARIFY EXISTING SUBPANEL LOAD AT GARAGE NOT | | | SHOWN ON CALCULATION AT THE 200A PANEL. SHOULD BE A | | | 60/2POLE BREAKER SHOWN AND LOADS REFLECTED. FBC 107.3.5 | | | | | | VAL PEREZ | | | *6717 |
|