| 2016-09-16 16:24:38 | CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA | | | BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION | | | | | | 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1 | | | INFORMATION ON CONSTRUCTION DOCUMENT | | | | | | I THINK YOU MAY HAVE THE SYSTEMS ON THE PLANS SWITCHED | | | AROUND. CHECK YOU CALCULATIONS AND CFM TOTALS. | | | | | | (1) AS PER THE LENNOX WEBSITE SYSTEM #1 - | | | CBX32M-018/024 BLOWER PERFORMANCE (208/230V) MAXIMUM | | | CFM IS 1100. TOTAL SUPPLY OUTLET CFM FOR SYSTEM #1 AS | | | PER PLANS IS1410 CFM. BALANCE CFM ON PLANS TO MEET THE | | | MANUFACTURERS SPECIFICATIONS. | | | (2) PROVIDE CONDENSER TIE DOWN DETAIL. | | | | | | | | | FLORIDA ENERGY CODE FBC 2014 | | | | | | (3) PROVIDE AHRI FOR EQUIPMENT SPECIFIED ON PLANS. | | | | | | JORGE VALIDO | | | WPB MECHANICAL INSPECTOR/PLANS EXAMINER | | | [email protected] | | | 561-805-6716 | | | | | | |
|