2016-09-16 16:24:38CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENT
  
 I THINK YOU MAY HAVE THE SYSTEMS ON THE PLANS SWITCHED
 AROUND. CHECK YOU CALCULATIONS AND CFM TOTALS.
  
 (1) AS PER THE LENNOX WEBSITE SYSTEM #1 -
 CBX32M-018/024 BLOWER PERFORMANCE (208/230V) MAXIMUM
 CFM IS 1100. TOTAL SUPPLY OUTLET CFM FOR SYSTEM #1 AS
 PER PLANS IS1410 CFM. BALANCE CFM ON PLANS TO MEET THE
 MANUFACTURERS SPECIFICATIONS.
 (2) PROVIDE CONDENSER TIE DOWN DETAIL.
  
  
 FLORIDA ENERGY CODE FBC 2014
  
 (3) PROVIDE AHRI FOR EQUIPMENT SPECIFIED ON PLANS.
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER
 [email protected]
 561-805-6716
  
  